StagingOrder numbers of all Firing boilers. If 
only one Firing boiler is found, or none are 
found, then this selection function returns a 
value that indicates no boiler may be dropped. 
Otherwise it returns an identifier for the boiler 
having the highest StagingOrder number
 
SEQUENCER 1 MINUTE EVENT 
Part of the sequencer is called by the timing 
service at a 1 minute rate to implement lead 
rotation. 
 
The 1 minute event checks the boiler identified 
by Lead- BoilerSeqNum. If it is Firing then the 
LeadBoilerRunTime 
is incremented. 
 
FORCED LEAD ROTATION: 
When the boiler identified by 
LeadBoilerSeqNum 
is firing and also 
LeadBoilerRunTime 
reaches the Force lead 
rotation time 
parameter time then: 
1. 
The current lead boiler is noted. 
2. 
Lead rotation occurs as described above 
under Voluntary Lead Rotation (this changes the 
designation, but does not change the actual 
firing status). 
 
SLAVE WRITE: DATA 
This allows the slave to accept command 
messages from a Sola master 
 
SLAVE READ: DATA 
This provides the slave status message to be 
read by a Sola Master. It includes all of the data 
that is read from a slave. 
 
SLAVE MODE: USE FIRST, EQUALIZE 
RUNTIME, USE LAST 
• If set to Use First, then this slave Sola will be 
used prior to using other slave Solas with other 
values. 
• If this parameter is set to Equalize Runtime, 
then this slave Sola will be staged according to a 
run time  equalization. (Any Solas set to Use 
First will precede  any that are set to Equalize 
Runtime.) 
• If this parameter is set to Use Last, then this 
slave Sola will be used only after 
• all Use First and Equalize Runtime Solas have 
been brought online. 
 
SLAVE PRIORITY SEQUENCE ORDER: 0-255 
Slave sequence order is used to determine the 
order in  which the slave Solas will be used 
(staged on) for those Solas with the same Slave 
mode setting. Numbers may be skipped, that is 
3 will be first if there is no 1 or 2. 
 
NOTE: For Equalize Runtime purposes, 1 does 
not mean the Sola will be used first every time; 
that will vary over time based on the master's 
run time equalization scheme. In this case the 
sequence number determines the relative  order 
in which Sola controls will be used in a  round-
robin scheme. 
 
If the slave sequence number value is zero, then 
the slave  Sola's ModBus address will be used 
instead. 
 
If two Solas are set the same mode and both 
have the  same sequence number then an alert 
will occur and the order in which they are used 
will be arbitrary and is not  guaranteed to be 
repeatable. 
 