calibrated.  When the screen is touched in a 
spot and unexpected results occur this is a good 
indication that the display needs to be 
calibrated.  To calibrate the touch screen select 
the ‘Calibrate’ button and follow the on screen 
directions.  Try using a stylus of some kind if the 
problem persists.  The eraser end of a pencil or 
the blunt end of a pen can be used as a good 
stylus. 
 
2.2.18 R
ESET 
/ R
EBOOT 
D
ISPLAY
 
► 1234 SETUP 
► ADVANCED SETUP 
► DISPLAY RESET 
 
Figure 32 Reset / Reboot Display 
 
The display can be reset or rebooted without 
powering down the boiler.  Select the ‘OK’ 
button and the display will reboot as shown in 
paragraph Power-up Validation 2.2.1. 
2.2.19 O
UTDOOR 
R
ESET
 
► ► CONFIGURE 
► OUTDOOR RESET 
► (page) CENTRAL HEAT 
 
Figure 33 Outdoor Reset 
 
Max outdoor temp 
(x
2
When the outdoor 
temperature is equal 
or greater than this 
value the boiler 
setpoint will be set to 
the low water 
temperature. 
Min outdoor temp 
(x
1
When the outdoor 
temperature is equal 
or less than this value 
the boiler setpoint will 
be set to the Central 
Heat Setpoint value 
(y
2
Low water temp 
(y
2
This value represents 
the water temperature 
setpoint when the 
maximum outdoor 
temperature is 
reached. 
Min water temp 
This value is used to 
override the low water 
temperature of the 
curve created with the 
above points without 
changing the slope. 
Max off point 
Undefined / Not Used 
 
25 
 
Select the ‘Show Line’ button to display a 
graphical representation for the inputted data