Bryan Boilers DST-50 プリント

ページ / 2
TM
BRYAN STEAM
Form No. 6410
(5/00)
15,000 PPH unit shown
Spray Type Boiler Feedwater Deaerators
Capacities 5,000 to 60,000 PPH (145 to 1740 BHP)
Performance Features
• Oxygen removal to .005 cc/l (7 PPB)
• CO
2
 removal to 0% measurable
• Reduce chemical costs
• Reduce boiler and system corrosion
• Improve boiler efficiency
• Pre-heat boiler feedwater
• Quick equipment payback,
compared to chemical oxygen removal
Construction Features
• Constructed to ASME Section VIII,
Division I for 50 PSIG
• Easily accessible manway
• Standard 10 minutes
deaerated water storage
• Internal vent condenser for minimum
steam loss
• Self-adjusting spring-loaded
stainless steel spray valve
• Structural steel stand/pump platform
• 2-stage deaeration
• Available as completely packaged unit
including pumps and control panel
The Bryan spray type deaerator is rated for oxygen
removal to .005cc/l (7 PPB) and CO
2
 to zero measur-
able across its entire operating range.  With its all
stainless steel spring loaded spray valve and second
stage steam scrubber, the spray type deaerator is a
good choice for all deaerator applications.
Units are available with a complete range of boiler
feedpumps and control options making them a total
deaerator package with minimal amount of field
assembly.
Integral
Tank Design
Horizontal
Tank Design