Regency Freestanding Woodstove
6
INSTALLATION
RESIDENTIAL 
INSTALLATION
1)  Please read this entire manual before you 
install and use your new woodstove. Failure 
to follow instructions may result in property 
damage, bodily injury or even death. Be 
aware that local Codes and Regulations may 
override some items in this manual. Check 
with your local inspector.
2)  Select a position for your Regency Stove. 
Consult the minimum clearance chart for 
your model and set the stove in place. For 
close clearance installation use listed double 
wall connector systems.
3)  To insure vertical alignment, suspend a 
plumb bob from the ceiling over the exact 
center of your stove fl ue and mark a spot 
on the ceiling to indicate the center of the 
chimney.
4)  Check that the area above the ceiling is clear 
for cutting. Re-confi rm the clearance from 
the stove to combustibles to insure that they 
are within the prescribed limits.
5)  This woodstove must be connected to a 
UL 103 HT (ULC S629) listed chimney or 
a code approved masonry chimney with a 
fl ue liner.
6)  Install chimney according to chimney manu-
facturers instructions. The performance of 
your woodstove is governed to a very large 
part by the chimney system. Too short a 
chimney can cause diffi cult start-up, dirty 
glass, backsmoking when door is open, and 
even reduced heat output. Too tall a chimney 
may prompt excessive draft which can result 
in very short burn times and excessive heat 
output. The use of an inexpensive fl ue pipe 
damper may be helpful in reducing excessive 
draft.
 CAUTION: The chimney should be the same 
size as the 6" fl ue outlet on the stove. The 
chimney must be listed as suitable for use 
with solid fuels. For other types of chimneys 
check with your local building code offi cials. 
Do not confuse a chimney with a type “B” 
Venting System used for gas appliances 
as suitable for a wood burning appliance. 
For Mobile Home installations refer to that 
section on page 14.
7)  Mark the location of the pedestal base or legs 
on the fl oor, then move the stove aside and 
mark the position of the fl oor protector.
8)  The fl oor protector must be of non-combus-
tible material and must extend 16"  in front 
of the door opening and 6"  to the sides and 
rear of the unit.  Some areas may require 
a larger size fl oor protector.  See your local 
inspector.  For outside air installation refer 
to Mobile Home installation instructions on 
page 14.
9)  When the fl oor protection is complete, posi-
tion the stove with the fl ue collar centered 
under the installed chimney.
10) In seismically active areas, Regency rec-
ommends that your unit is secured to the 
fl oor by using the bolt down holes inside 
the pedestal (the same ones used in Mobile 
Home installations).
11)  For residential installations using 6" (152mm) 
"C" Vent (single wall) the chimney connector 
must be at least 24 gauge steel. Do not use 
galvanized pipe. For Mobile Home installa-
tion refer to the Mobile Home installation 
instructions on page 14.
12) Do not connect this unit to a chimney 
serving another appliance.
13) A chimney connector cannot pass through 
an attic or roof space, closet or similar 
concealed space, or a fl oor, ceiling, wall 
or partition of combustible construction. In 
Canada, if passage through a wall, or parti-
tion of combustible construction is desired, 
the installation shall conform to CAN/CSA-
B365, Installation Code for Solid-Fuel-Burn-
ing Appliances and Equipment.
14) Your Regency Woodstove is not to be con-
nected to any air distribution duct.
Emissions from burning  wood or gas could 
contain chemicals known to the State of 
California to  cause cancer, birth defects 
or other reproductive harm.
NOTE: In Canada, fl oor protection must 
extend 18" (450mm) to the front and 
8" (200mm) to each side and back 
of the stove.
MODULAR INSTALLATION OPTIONS
Modular Part
Things to consider when choosing options:
Modular Option
Blower/Fan
Ash Drawer Kit
Screen Door
OPTIONS: These can be installed at time of installation or added later:
Airmate OR 
Rear Heat Defl ector
Pedestal OR
Legs
Things to consider when choosing options
The following items are required when assembling your Regency Stove.  F2402M unit - the Rear Heat Defl ector is supplied with the stove, but if 
you choose not to use it you must use the Airmate instead.  
Clearances are different. Generally you can get closer clearances with the airmate than with the rear heat defl ector.
Convection heat with Airmate vs. Radiant Heat with Rear Heat Defl ector. The airmate pushes heat forward and into 
the room, the rear heat defl ector defl ects the heat upward.
There are no performance differences with either the pedestal or legs.  It is primarily a personal preference.  Legs can 
be either painted steel, painted cast, or gold plated cast.  
Leg installation requires the bottom shield. 
Adding the blower will increase the area heated by the stove, it can move warm air beyond the room where the stove 
is installed. 
Adding the Ash Drawer Kit makes cleaning ashes out of the stove easier and cleaner.  
A simple add-on option that will allow you to enjoy the sound, warmth and view of an open fi re.