 U39 ULTIMATE Direct Vent Freestanding Gas Stove
9
EXTERIOR VENT TERMINAL LOCATIONS
A
=
 
Clearance above grade, veranda, porch, deck, or balcony *(min.
 
12"/30cm) 
B= 
Clearance to window or door that may be opened *(12"/30cm)
C= 
Clearance to permanently closed window *(min. 12"/30cm) 
D= 
V
ertical clearance to ventilated soffi
 t located above the terminal within a 
horizontal distance of (24"/60cm) from the centerline of the terminal (min. 
18"/46cm) check with local code.
E= 
Clearance to unventilated soffi
 t 
(min. 
12"/30cm)
F= 
Clearance to outside corner: with 
AstroCap
 T
e
rmination Cap (min. 6"/15cm), 
with Dura-V
ent termination cap (min. 12"/30cm)
G= Clearance 
to 
inside 
corner: 
with 
AstroCap
 T
e
rmination Cap (min. 6"/15cm), 
with Dura-V
ent termination cap (min. 12"/30cm)
H= 
Not to be installed above a meter/regulator assembly within (3'/90cm) 
horizontally from the centerline of the regulator
.
J= 
Clearance to service regulator vent outlet *(min. 36"/90cm)
K= 
Clearance to non-mechanical air supply inlet to building or the combustion 
air inlet to any other appliance *(12"/30cm)
L= 
Clearance to a mechanical air supply inlet *(min. 72"/1.8m)
M= 
**Clearance above paved sidewalk or a paved driveway located on public 
property *(min. 84"/2.1m)
N= 
Clearance under veranda, porch, deck, or balcony *(min. 12"/30cm)***
    
Note: * 
As specifi
 ed in CGA
 B149 Installation Code.  Note: Local codes or  regulations may require dif
ferent clearances.
**A
 vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings a
nd serves both dwellings.
INSTALLATION