Ei Electronics Ei151TLR プリント

ページ / 2
 
Shannon Free Zone, Shannon, Co. Clare, Ireland. 
Ph.
+353 61 471277   
Fx.
+353 61 471053   
 
Email.
 eielectronics@eiltd.ie
 
 
Web:
 www.eielectronics.com 
E & OE  As our policy is one of continuous product development, we reserve the right to alter product details without prior not ice
.       
Ei151TLR DataSht RevB
 
 
Model 
Ei 151TLR Ionisation 
 
Remote control capability 
 
Tamper proof rechargeable lithium battery back up 
 
High performance ionisation chamber  
 
Test/Hush button 
 
Advanced suppression and calibration technology 
 
Interconnectable to other Ei mains powered alarms 
 
Low power cell warning 
 
Kitemarked to BS EN 14604:2005 
 
5 year guarantee 
 
 
Product Description 
 
The Ei151TLR is an Ionisation Smoke Alarm that runs on 
230V AC mains power, and has built in tamper proof 
rechargeable lithium cells that act as a battery back up in 
the event of mains failure. These rechargeable lithium 
cells are designed to have a ten year life and outlast the 
life of the smoke alarm itself, whilst providing up to six 
months of smoke alarm operation without mains power. 
 
The Ei151TLR allows the detector to be controlled 
remotely by either a “Test/Hush” Switch (Ei152), a 
“Locate” Switch (Ei159) or a Manual Call Point 
(MCP400). If the Ei151TLR is also interconnected to 
other Ei mains powered alarms then the whole system 
will be controllable remotely. 
 
The Ei151TLR has the ability to interconnect up to twelve 
alarms to allow all alarms to sound if just one of the 
interconnected alarms should be triggered. 
 
The Ei151TLR has built in circuitry to aid suppression of 
voltage transients and RF interference to further reduce 
the chances of false alarms under such conditions. 
 
Operation 
 
 
The green indicator will illuminate to show mains 
power is present 
 
 
The red indicator will flash rapidly to show an alarm 
condition for the smoke detector 
 
 
The “Test/Hush” button will either silence false 
alarms or perform a unit self test. In “Test” mode the 
alarm will perform a self test and sound the horn  
 
 
In “Hush” mode the alarm enters a ten minute period 
of reduced sensitivity to overcome false alarm 
conditions, and will then automatically reset itself 
 
 
When interconnected to other Ei mains powered 
alarms, an alarm on one detector will trigger all other 
interconnected alarms within one second (only the 
triggered alarm will flash a red indicator) 
 
 
The smoke detector will emit a beep and flash the 
red light every 40 seconds to indicate that the 
battery back up is depleted and needs recharging 
 
 
The detector can be controlled remotely by either a 
“Test/Hush” Switch (Ei152), a “Locate” Switch 
(Ei159) or a Manual Call Point (MCP400). 
 
 
MAINS POWERED 230V~ 
Rechargeable Battery Back-Up