DS9400 Series | Release Notes for Firmware V2.07 | 7.0 
Fixed Items Since Firmware Version 1.08 
 
 
Bosch Security Systems | 8/06 | 36925V 
 
 
DS9431 Accidental Removal (DS9400M 
only): On control panels running firmware 
version 2.02 or earlier, if the wires on the 
keypad option bus are momentarily shorted for 
less than a second, the DS9431 Multiplex 
Expansion Module may stop working. If this 
occurs, the display will show “MUX NOT 
DETECTED” and the Trouble buzzer will 
sound. If the */Clear key is pressed, the DS9431 
will be uninstalled. 
Firmware version 2.03 corrects this problem. If 
the DS9431 should fail, a new message, “CALL 
FOR SERVICE,” will be displayed along with 
the following message, “MUX NOT 
WORKING.” Pressing the */Clear key will 
silence the Trouble buzzer, but will neither clear 
the trouble messages nor uninstall the DS9431. 
If “MUX NOT WORKING, CALL FOR 
SERVICE” or INST.FLT MX EXP” is 
displayed, the control panel should be powered 
down by removing AC and standby battery 
connections, and then restarted. Doing so will 
restore the DS9431 to proper operation. If the 
problem is not corrected, please contact 
Technical Support at (888) 886-6189. 
 
 
Make sure that you are at the control panel 
site with an available phone line before 
calling Technical Support. 
 
To remove the DS9431 after installing firmware 
version 2.03, please contact Technical Support at 
(888) 886-6189. 
 
DS9434 Four Point Expander Removal: To 
prevent the accidental removal of the DS9434, a 
new message “CALL FOR SERVICE,” is 
displayed. If you wish to remove a previously 
installed DS9434, please contact Technical 
Support at (888) 886-6189. 
7.0  Fixed Items Since 
Firmware Version 1.08  
 
AC Failure during Automatic Battery Test: 
The DS9400 FACP automatically tests the 
standby batteries every 180 seconds for two 
seconds. The system will now continue normal 
operation if an AC power failure occurs exactly 
during this two-second battery test window. 
 
 
Boards shipped before August 31, 1999 
must be modified according to Technical 
Service Note (P/N: 42363) to ensure that 
the battery test runs properly. Affected 
boards carry a lot number of 99 or lower 
and a date code of 9935 or earlier. Boards 
shipped after August 31, 1999 with a date 
code higher than 9935 are unaffected. See 
Figure 1 on page 3 for the location of the 
lot number and date code. 
 
 
 
Figure 1: 
Firmware Version Label and Date 
Code Locations 
XXXX
2
1
3
 
1
 
Lot Number Label 
2
 
Firmware Version Label 
3
 
Date Code Stamp 
 
 
Do not exceed standby current ratings for 
the control panel. If the total current drawn 
from the smoke power and option bus 
power terminals exceeds 1 amp, the 
system may not be able to switch to battery 
power when AC fails. Current drawn from 
NACs and auxiliary power does not impact 
battery transfer operation.