Bosch FPD-7024 ユーザーズマニュアル

ページ / 122
Several keys assist when you enter phone or IP numbers. For these keys, see the following
table:
Press
Action
[SILENCE]
Advance to next position
[DISABLE]
Go back one position
[RESET]
Clear position
Table 8.4: Phone number assistance keys
i
Notice!
For a phone number, you must enter 1 as a prefix before the special character >. Except for
unusual situations, all phone numbers should have the wait for dial tone character as the sec-
ond digit. This ensures that reports are delivered as quickly as possible, even if an incoming
phone call must be disconnected. For example, you would program 1>18002890096 for the
phone number 1 800-289-0096.
If the wait for dial tone is not specified, the control panel waits 7 sec after going off-hook,
and then dials whether or not the dial tone is present.
 
To enter a central station IP address in either phone number 1 or 2 in the control panel,
replace all three phone numbers with an IP address. To distinguish an IP address from a
phone number, enter 0 as the first digit, followed by the 12 digit IP address.
i
Notice!
The IP address must be 12 digits long.For example, if the IP address is 172.30.1.101, the
phone number is programmed as 0 172 030 001 101. Do not add the spaces. They are inclu-
ded for readability.
 
For programming an IP address and bit locations, see the following table:
Digit 1
Digit 2
Digit 3
Digit 4
Digit 5
Digit 6
Digit 7
Digit 8
0 = Alt.
Comm.
On
IP1
IP2
IP3
IP4
IP5
IP6
IP7
Digit 9
Digit 10
Digit 11
Digit 12
Digit 13
Digit 14
Digit 15
Digit 16
IP8
IP9
IP10
IP11
IP12
Ack Wait
N2
Ack Wait
N1
Ack Wait
N0
Digit 17
Digit 18
Digit 19
Digit 20
Digit 21
Digit 22
Digit 23
Digit 24
HB
interval
N2
HB
interval
N1
HB
interval
N0
1 = Anti-
Replay On
0 unused
0 unused
0 unused
0 unused
Table 8.5: IP address digit or bit location
Acknowledge Wait Time (ACK) – Digits 14 to 16, Default: 010
The alternate communication event, transmission acknowledge wait time, is stored in the
phone number location as digits 14, 15 and 16. The wait time is a number from 1 to 255
seconds where the most significant or first digit is D14.
 
 
Fire Alarm Control Panels
Control Panel Programming | en
79
Bosch Security System, Inc.
Installation and Operation Manual
2012.08 | 04 | F01U008458