LST BC216-1S ユーザーズマニュアル

ページ / 3
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
BC216-1S_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
Description
•  1-loop version of BC216-1
•  For the application in small systems
•   Analogue ringbus technology with 
unshielded detector cabling
•  Menu-driven operation
•   Easy commissioning through 
AUTO setup
•  32–bit multiprocessor system
•  EN 54/VdS-certifi ed
Fire is a permanent threat to life and property. There-
fore, immediate response to a fi re is imperative. The 
main  objective  of  fi re  detection  control  panel  Series 
BC216  is  to  alarm  and  to  react  in  time  and,  conse-
quently, save lives and protect property. For decades 
LST have focused their aims to undertaking unrivaled 
efforts in order to realize new innovations in the security 
area. Research, development and production are loca-
ted within LST premises, thus guaranteeing fl exible and 
reliable individual solutions.
Using a 32-bit multiprocessor system, the fi re detection 
control panel Series BC216 ensures topmost effi ciency 
and speed – prerequisites for saving lives and minimi-
zing damage to property.
The fi re detection control panel BC216–1S is designed 
to be used in small systems with only one ADM loop. It 
comprises  an  already  completely  mounted  unit  which 
includes all basic components that are needed for the 
operation of a 1-loop fi re detection control panel.
Slot  1  is  by  default  equipped  with  a  Loop  Interface 
LIF64-1 for the connection of an ADM loop, slot 2 is 
inoperable.
The ADM loop principle offers intelligent analogue ring-
bus  technology  with  bi-directional  data  transfer.  The 
loop provides for the software-aided administration of 
up to 198 physical address points in a maximum of 128 
detector zones. Conventional detectors can be integra-
ted into the ADM loop, if required, by means of conven-
tional zone modules.
Depending on the respective system, a Fire Brigade In-
terface FWI2-1, a Fire Brigade Interface Additional Board 
FWZ2-1, an LED-Display Field LAB48 as well as further 
optional componentries can be installed in addition.
Easy  parameterisation  on  the  control  panel‘s  display 
and operating unit, via a PC keyboard, or by means of 
a PC software enables you to tailor the control panel to 
your individual requirements.