Honeywell 5820XL ユーザーズマニュアル
IntelliKnight 5820XL Installation Manual
7-22
151209
SWITCH
(cont.)
ZN_AUX1
Latching
Use these switch types if you want to monitor special zone-level conditions
(such as operation of a fan or damper).
(such as operation of a fan or damper).
Non Latching
ZN_AUX2
Latching
Non Latching
SYS_AUX1
Latching
Use these switch types if you want to monitor special system-wide
conditions (such as operation of a fan or damper).
conditions (such as operation of a fan or damper).
Non Latching
SYS_AUX2
Latching
Non Latching
DETECT SW
Used to monitor conventional 4-wire detectors, a contact closure will
generate a detector alarm event.
generate a detector alarm event.
TAMPER
Latching
Performs identically to a supervisory switch, but will be indicated as a
tamper switch on the LCD annunciator.
tamper switch on the LCD annunciator.
Non Latching
MAN REL
Latching
Manual release switch, typically a pull station.
Non Latching
ILOCK
Latching
Interlock release switch input.
Non Latching
NOTIF
OUTPUT PT
Select Group
Output Point, a general use notification type. Use for driving standard
notification appliances.
notification appliances.
AUX CONST
Use constant power for applications that require a constant auxiliary power
source. Power is always present at Constant circuits.
source. Power is always present at Constant circuits.
AUX RESET
Use for auxiliary power, resettable applications. See Section 4.13.5.3 for a
description of how this option operates.
description of how this option operates.
AUX DOOR
Use for auxiliary power, door holder applications. For example, if you were
using an auxiliary power supply for door holders, you would use this option.
See Section 4.13.5.1 for a description of how this option operates.
using an auxiliary power supply for door holders, you would use this option.
See Section 4.13.5.1 for a description of how this option operates.
RELAY
OUTPUT PT
Select Group
Output Point, a general use relay type. Use for applications requiring a relay,
such as fan shutdown, elevator recall, and so on.
such as fan shutdown, elevator recall, and so on.
AUX RESET
Select Group
Use for auxiliary power, resettable applications. See Section 4.13.5.3 for a
description of how this option operates.
description of how this option operates.
AUX DOOR
Select Group
Use for auxiliary power, door holder applications. For example, if you were
using an auxiliary power supply for door holders, you would use this option.
See Section 4.13.5.1 for a description of how this option operates.
using an auxiliary power supply for door holders, you would use this option.
See Section 4.13.5.1 for a description of how this option operates.
Table 7-5: Point Programming Options for 5815XL Modules
Type
Selection
Function
Latching
Option
Comments