IntelliKnight 5820XL Installation Manual
3-14
151209
U
Select alarm delay options (detection characteristics) for zone.
U
Select heat detector trip temperature. (JumpStart selects 150°F for heat 
detectors.)
Output Point Configuration
Conventional notification circuits (circuits 1-6): 
U
Enable circuits used for notification appliances through programming, if 
necessary. (JumpStart enables circuits 1-6 as Notification.)
Conventional relay circuits (circuits 7-8):
U
Select options for relay circuits, if desired. Note: Relay circuits will always 
output continuously (constant pattern), even if assigned to an Output Group 
that uses a different output pattern.
Auxiliary power circuits (circuits 1-6):
U
Enable any circuit used for auxiliary power devices through programming.
U
Select type of power (door holder, constant, or resettable)
Addressable relay modules
U
Assign addressable relay modules to output groups through programming. 
(JumpStart assigns all relay modules to Group 1.)
LED output points (from the 5880 LED I/O module or 5865/66 LED Annunciator)
U
Assign LED modules to output groups through programming. 
All output circuits (1-8):
U
Disable (set to UNUSED) any unused circuits. If you do not disable unused 
output circuits, they will cause a trouble condition (unless an EOL resistor 
is used).
U
Select a name for the point, if desired.
Output Group Configuration
U
Add the group to the system if it does not already exist.
U
Assign output points to the group.
U
Program a name (or description) for the group, if desired.
Select “group properties” (see below).
U
Latching / non-latching
U
Silencing option
U
Select options for activation with system switches.
U
Map zones to output groups that will activate when zone goes into alarm.
U
Select a cadence pattern for outputs in the zone.
Task
See Sec.
(for more info.)