Honeywell 25/50ZST ユーザーズマニュアル

ページ / 144
Audio Command Center Series Manual — P/N 51889:E1  6/8/2010
109
MS-9600, MS-9200UDLS and MS-9200UD
Programmed Activation by FACP
D.1.5  FACP Programming
The MS-9600, MS-9200UDLS, and MS-9200UD FACPs must be programmed to operate with the 
ACC-25/50ZS or ACC-25/50ZST Audio Control Center.  The following table summarizes the steps 
involved in programming the FACPs.  A detailed description of each step follows the table.
ACS Annunciator
The ACC-25/50ZS and ACC-25/50ZST communicate with the FACP via the ACS link.  Enable the 
ACS Annunciator address 01 as described in the appropriate FACP manual.  For ACC-25/50ZST 
using annunciation of remote FFTs, enable address 05 for the MS-9200UDLS and address 07 for 
the MS-9600.  The ACS programming options can be accessed by entering Programming Mode 
and selecting Option Modules from the list of programming options.
ANN-BUS Annunciator
The ACC-25/50ZS and ACC-25/50ZST communicate with the FACP via the ANN-BUS link.  
Auto-configure the ANN-BUS Annunciator as described in the appropriate FACP manual.  The 
ANN-BUS programming options can be accessed by entering Programming Mode and selecting 
Option Modules from the list of programming options.
Zone Assignment
Zones must be assigned to each addressable input device in order to activate the appropriate output 
device(s).  Program each device to a zone as described in the appropriate FACP manual.  Device 
programming can be accessed by entering Programming Mode and selecting Point Program from 
the list of programming options.
Note that when the ACS/ANN-BUS Annunciator option is enabled at the FACP, speaker circuits at 
the ACC-25/50ZS or ACC-25/50ZST are automatically assigned dedicated zone numbers.  These 
zone numbers can then be programmed to addressable input devices which will allow the input 
device to activate the programmed speaker zone.  
The following table lists the zone numbers that are automatically assigned to each speaker circuit. 
Note that the ACC-ZSM Zone Splitter Module installed in the ACC-25/50ZS or ACC-25/50ZST 
provides 8 Style Y (Class B) speaker circuits.  Additional speaker circuits can be added using the 
ACC-25/50DAZS.
1.
Enable the ACS or ANN-BUS annunciator at FACP
refer to FACP manual Option Module Programming
2.
Assign zone(s) to each addressable device
refer to FACP manual  Point Programming
3.
Program message to be generated over each speaker circuit
refer to Message Assignment in following section
4.
Activate individual devices to ensure proper programming
compare to desired programming
Table D.4  FACP Programming Steps
Speaker Circuit Number
Zone Number
All Speaker Circuits (1-24)
32
1 (on ACC-25/50ZS/T)
33
2 (on ACC-25/50ZS/T)
34
3 (on ACC-25/50ZS/T)
35
4 (on ACC-25/50ZS/T)
36
5 (on ACC-25/50ZS/T)
37
6 (on ACC-25/50ZS/T)
38
7 (on ACC-25/50ZS/T)
39
8 (on ACC-25/50ZS/T)
40
Table D.5  Speaker Circuit Zone Assignments