A.O. Smith BFM 80 ユーザーズマニュアル

ページ / 32
10
Description
Unit
BFM 30
BFM 50
BFM 80
DATA NATURAL GAS G 20
Nominal gas inlet pressure
mbar
20
20
20
Burner pressure
mbar
12.5
12.5
12.5
Input
kW
29
47
75
Output to water
kW
27
42
68
Gas consumption*
m3/h
3.0
4.7
7.9
Diameter main injector
m m
2.60
2.50
2.70
Diameter  injector  ignition  burner
m m
0.56 / 0.41
0.56 / 0.41
0.56 / 0.41
Heating time 
T=45°C
min
35
25
12
DATA PROPANE/BUTANE G 30 - G 31
G30
G31
G30
G31
G30
G31
Nominal gas inlet pressure
mbar
30
37
30
37
30
37
Input
kW
29
28
46
44
75
71
Gas consumption
kg/h
2.3
2.1
3.6
3.3
5.8
5.3
Diameter main injector
m m
1.45
1.40
1.50
Diameter injector ignition burner
m m
0.25
0.25
0.25
GENERAL
Storage capacity
litre
309
298
253
Number of bar burners
-
3
5
7
Number of anodes
-
2
2
4
Number of flue tubes
-
5
7
16
Water connections
-
Rp11/2
Rp11/2
Rp11/2
Gas connection
-
Rp3/4
Rp3/4
Rp3/4
Drain  connection
-
3/4" - 14 NPT
3/4" - 14 NPT
3/4" - 14 NPT
Anode
-
3/4" - 14 NPT
3/4" - 14 NPT
3/4" - 14 NPT
Connection  T&P-plug**
-
1” - 14 NPT
1” - 14 NPT
1” - 14 NPT
Maximum working heat
bar
8
8
8
Empty weight
kg
270
290
350
1.3.2 Technical data
Heater category:II  
2H3+
* Gas usage at 1013,25 mbar and 15 °C.
** For a leak-tight connection European coupling pieces with pipe screw-thread according to ISO 228/1 or ISO 7/1 can be
used on the NPT-connection nipples.