Bosch MIYN46 ユーザーズマニュアル

ページ / 28
14
en | Installation
MIYN46 Wall Transmitter
970.035b | F.01U.278.521 | v2.0 | 2012.12
User Manual US
Bosch Security Systems
4.2.8
Configuration and Wiring
Fig. 4.2
Configuration and Wiring
J4
J5
J6
1 2 3 4 5 6
1
2
3
4
5
Terminal J5
1 External 12-24 VDC power supply
5-6 REL 2 Staff Presence
2 GND (0 V)
3-4 REL 1 Call for Help
Terminal J6:
4-5 Reserve Call or Call for Assistance
3-4 Technical Alarm
1-2 Call for Help
Connector J4:
External Call for Help
trigger (pear push button)
Solder Bridges (if soldered):
B8 Call for Assistance only by
B7
B6 No
processing
B5 No Daily Message
B4 Not used
B3 Not used
Staff Presence
Call for Assistance from terminals J6[4-5]
Staff Presence
B1 REL 1 Call for Help
B2
REL 2 Staff Presence
(o)
(o)
polarity
polarity
N
NC
N
NC
NC
NO
NC
NO
J2 Polarity of Technical Alarm input
J3 Polarity of
input
terminal J6[4-5]
Connector J7:
Presence / Staff identification (optional)
N
NC
J1 External Call for Help trigger
input polarity
CR 2450
battery
Reset
NC-B2-NO            NC-B1-NO
Solder bridges B1 and B2 are located on the bottom side of the PCB:
(o)
i
NOTICE! 
Setting up one or more inputs to "NC" position results to higher power consumption. This con-
figuration should be used with external power supply or will reduce the battery life.