Honeywell R7886A ユーザーズマニュアル

ページ / 8
PRODUCT DATA
65-0109-8
® U.S. Registered Trademark
Copyright © 2002 Honeywell •  All Rights Reserved 
R7824, R7847, R7848, R7849,R7851,R7861,
 R7886 Amplifiers for
7800 SERIES Relay Modules
 
APPLICATION
The R7824C Rectification Flame Amplifier is a solid state plug-in 
amplifier that responds to a rectified signal from a C7024E,F Self-
Check Ultraviolet Flame Detector to indicate the presence of 
flame when used with an RM7824 Relay Module.
The R7847A,B Rectification Flame Amplifiers are solid state plug-
in amplifiers that respond to a rectified signal from a rectification 
type flame detector to indicate the presence of flame when used 
with 7800 SERIES Relay Modules.
The R7847C Self-Check Rectification Flame Amplifier is a solid 
state plug-in amplifier that responds to a rectified signal from a 
C7012E,F Self-Check Ultraviolet Flame Detector to indicate the 
presence of flame when used with 7800 SERIES Relay Modules. 
This is not European Community (CE) approved for EC7810, 
EC7820, EC/RM7830 or EC/RM7850 Relay Modules.
The R7848A,B Infrared Flame Amplifiers are solid state plug-in 
amplifiers that respond to an infrared signal from a C7015 
Infrared Flame Detector to indicate the presence of flame when 
used with 7800 SERIES Relay Modules.
The R7849A,B Ultraviolet Flame Amplifiers are solid state plug-in 
amplifiers that respond to an ultraviolet signal from a C7027, 
C7035 or C7044 Ultraviolet Flame Detector to indicate the 
presence of flame when used with 7800 SERIES Relay Modules.
The R7851B Optical Flame Amplifiers are solid state plug-in 
amplifiers that respond to optical signals from C7927, C7935, 
C7915, and C7962 Flame Detectors to indicate the presence of 
flame when used with 7800 SERIES Relay Modules.
The R7851C Dynamic Self-Check Optical Flame Amplifier is a 
solid state plug-in amplifier that responds to ultraviolet signals 
from C7961E Dynamic Shutter-Check ultraviolet flame detectors 
to indicate the presence of flame when used with 7800 SERIES 
Relay Modules.
The R7861A Self-Check Ultraviolet Flame Amplifier is a solid 
state plug-in amplifier that responds to an ultraviolet signal from a 
C7061 Self-Check Ultraviolet Flame Detector to indicate the 
presence of flame when used with 7800 SERIES Relay Modules.
The R7886A Dynamic Self-Check Ultraviolet Amplifier is a solid 
state plug-in amplifier that responds to a pulsed direct current 
signal from a C7076A,C Ultraviolet Flame Detector with 
adjustable sensitivity to indicate the presence of flame when used 
with 7800 SERIES Relay Modules.
FEATURES
• Flame failure response time of 0.8 or 1 second; or 2.0 or 
3.0 seconds, depending on the amplifier and relay module 
selected. See Table 1.
• Plug-in to 7800 SERIES Relay Module through printed 
circuit board edge connector keyed for proper orientation.
• Flame signal test jacks measure amplifier flame signal 
voltage.
• 0.0 to 5.0 Vdc Flame signal strength reading range.
• Color coded label identifies flame detection type:
Green—rectification. Red—infrared.
Purple—ultraviolet. Blue—pulsed rectification.
White—optical.
• R7847B, R7848B, R7849B Dynamic Ampli-Check® 
circuitry tests all flame amplifier components 12 times per 
minute. The 7800 SERIES Relay Module locks out on 
safety shutdown with amplifier failure.
• R7824C and R7847C Dynamic Self-Check Rectification 
Amplifier, R7851C Dynamic Self-Check Optical Flame 
Amplifier, R7861 Self-Check Ultraviolet Flame Amplifier 
and R7886A Dynamic Self-Check Ultraviolet Amplifier test 
the detectors and all electronic components in the flame 
detection system 12 times per minute. The 7800 SERIES 
Relay Module locks out on safety shutdown with flame 
detection system failure. 
NOTE:
NOTE:R7824C, Series 2 or greater, and R7847C, 
Series 4 or greater, pulse shutter when signal of 
1.5 Vac is sensed.
Contents