Fig. 34. T7300D,F/Q7300L2004 for two-stage heating with three-position 
ML7984 Valve Actuator and V5013B Valve and one-stage cooling.
GH
L1
(HOT)
L2
POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND OVERLOAD 
PROTECTION AS REQUIRED.
INDEPENDENT FAN TRANSFORMER IS OPTIONAL. JUMPER FC TO R 
WHEN SINGLE TRANSFORMER IS USED.
REFER TO ML7984 INSTRUCTIONS FOR TERMINAL CONNECTIONS.
T7047 HAS T-T TERMINALS ONLY.
180 
  
  2W RESISTOR MUST BE INSTALLED AS SHOWN.
1
M4950B
T
A1
RM
Y
SUBBASE
1
R
FC
C1
T
T7147 REMOTE COMFORT ADJUST MODULE
GND
GL
C2
L1
(HOT)
L2
1
2
2
C4
C3
C5
T
CA1
T
CA2
CA4
CA3
CA5
A2
COOLING 
RELAY
X
P2
P1
BM
LOW
SPEED
FAN 
RELAY
DAMPER
CONTROL
RELAY
PUMP
INTERLOCK
RELAY
3
9
3
4
7
5
6
7
8
9
8
4
6
HIGH 
SPEED
FAN 
RELAY
ML7984 
VALVE
ACTUATOR
R1
B3
W
T5
T6
5
TRANSFORMER
FAN
TRANSFORMER
AS
AS
DISCHARGE
AIR
SENSOR
CONNECT GND TO EARTH GROUND.
DISCHARGE AIR SENSOR IS ONLY COMPATIBLE WITH T7300F 
THERMOSTAT.
JUMPER GH AND GL FOR SINGLE SPEED FAN.
SET THE DIP SWITCHES ON THE ML7984 TO MECHANICAL
SERIES 90 TO USE WITH Q7300L