Bradford-White Corp ULTRA HIGH EFFICIENCY COMMERCIAL GAS WATER HEATER ユーザーズマニュアル

ページ / 76
34 
It is acceptable to install a 90 degree elbow on IPEX concentric vent terminations use with this power direct 
vent water heater (see Figure 23b). A short length of appropriate diameter vent pipe should be used to 
transition from the vent terminal to the 90 degree elbow. Approved venting materials along with primers and 
cements are listed at the beginning of this venting section. When the 90 degree elbow is used the equivalent 
length of the elbow and short length of vent pipe must be factored into the total vent/air intake pipe 
determinations (see Tables 3 and 4 for appropriate vent connector lengths). 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
WARNING! DO NOT 
USE 2” VENT WITH 
EF100T250/300 
MODELS 
Figure 23B
 
 
 
 
 
 
 
VENT PIPE PREPARATION 
 
 
WARNING
 
DO NOT attempt to start this water heater until vent pipe solvent fumes completely clear from the room and inside the 
vent piping. 
(A) VENT DIAMETER 
(B) DIMENSION 
 MIN 
MAX 
2” (5.1 CM) 
12” (30.5 CM) 
40” (101.6 CM) 
3” (7.6 CM) 
12” (30.5 CM) 
44” (111.8 CM)