CN 211/215 UIM Communication Cable:
•  Pin 1 - +5 V
•  Pin 2 - +12 V
•  Pin 3 - Signal A+
•  Pin 4 - Signal B+
•  Pin 5 - Ground
Note: 
Both CN211 and CN215 are identical and either can be used for the UIM communication.
CN 208 Overload Detection:
•  Pin 1 - High pressure switch.
•  Pin 2 - High pressure switch.
•  Pin 3 - Low pressure switch.
•  Pin 4 - Low pressure switch.
•  Pin 5 - Not used
•  Pin 6 - Not used
•  Pin 7 - Not used
•  Pin 8 - Not used
•  Pin 9 - Condensate pump signal overfl ow (optional)
•  Pin 10 - Condensate pump signal overfl ow (optional)
Note: 
Pin 9 and 10 are connected by a jumper wire. This wire should be cut and wired in series to 
the overfl ow switch of the fi eld supplied condensation pump (optional).
SW 201 Dip Switch:
•  SW 1 - Not used
•  SW 2 - Not used
•  SW 3 - Not used
•  SW 4 - Not used
Led 201 Power Indicator:
•  LED 201 when illuminated, indicate that 5 and 12 Volts DC are present for the UIM
Section D
LED 202/203 Powered Anode Indicators:
• LED 
202- 
One (1) fl ash/second (approx.), indicates 
there is power to the anode circuit.
• LED 
203- 
Two (2) fl ashes/second (approx.), indicates 
proper operation. 
Four (4) fl ashes/second (approx.), 
indicates a fault. 
Figure 9
LED
203 / 202
Section D
Section “C” of Control Board (con’t)