4.  When  installing  multiple  water  heaters  in  the  same  gas 
supply  system  it  is  recommended  that  individual  positive 
lock-up gas pressure regulators be installed at each unit.
power supply
The water heaters covered in this manual require a 120 VAC, 
1Ø (single phase), 60Hz, 15 amp power supply and must also 
be electrically grounded in accordance with local codes or, in the 
absence of local codes, with the national electrical Code, AnSI/
nFPA 70 or the Canadian electrical Code, CSA C22.1.
water temperature Control and miXing ValVes
Water temperature over 125°F (52°C)
can cause severe burns instantly
resulting in severe injury or death.
Children, the elderly and the
physically or mentally disabled are at
highest risk for scald injury.
Feel water before bathing or
showering.
Temperature limiting devices such as
mixing valves must be installed
when required by codes and to
ensure safe temperatures at fixtures.
Water heated to a temperature which will satisfy clothes washing, 
dish washing, and other sanitizing needs can scald and cause 
permanent  injury  upon  contact.  Short  repeated  heating  cycles 
caused by small hot water uses can cause temperatures at the 
point of use to exceed the water heater’s temperature setting by 
up to 20°F (11°C).
Some  people  are  more  likely  to  be  permanently  injured  by 
hot  water  than  others. These  include  the  elderly,  children,  the 
infirm  and  the  physically/mentally  disabled. Table  5  shows  the 
approximate  time-to-burn  relationship  for  normal  adult  skin. 
If  anyone  using  hot  water  provided  by  the  water  heater  being 
installed fits into one of these groups or if there is a local code 
or state law requiring a certain water temperature at the point of 
use, then special precautions must be taken.
In addition to using the lowest possible temperature setting that 
satisfies the demand of the application a Mixing Valve should be 
installed at the water heater (see Figure 10) or at the hot water 
taps to further reduce system water temperature.
Mixing valves are available at plumbing supply stores. Consult 
a  qualified  Installer  or  Service  Agency.  Follow  mixing  valve 
manufacturer’s instructions for installation of the valves.
taBle 5.
water temperature 
°f (°C)
time for 1st degree Burn 
(less Severe burns)
time for permanent Burns 
2nd & 3rd degree 
(Most Severe burns)
110 (43)
(normal shower temp.)
116 (47)
(pain threshold)
116 (47)
35 minutes
45 minutes
122 (50)
1 minute
5 minutes
131 (55)
5 seconds
25 seconds
140 (60)
2 seconds
5 seconds
149 (65)
1 second
2 seconds
154 (68)
instantaneous
1 second
(U.S. Government Memorandum, C.P.S.C., Peter l. Armstrong, Sept. 15, 1978)
gas supply systems
low pressure building gas supply systems are defined as those 
systems that cannot under any circumstances exceed 14” W.C. 
(3.49  kPa)  (1/2  PSI  Gauge).  These  systems  do  not  require 
pressure regulation. Measurements should be taken to insure 
that gas pressures are stable and fall within the requirements 
stated  on  the  water  heater  rating  plate.  readings  should  be 
taken with all gas burning equipment off (static pressure) and 
with all gas burning equipment running at maximum rate (dynamic 
pressure). The gas supply pressure must be stable within 1.5” 
W.C. (0.37 kPa) from static to dynamic pressure to provide good 
performance. Pressure drops that exceed 1.5” W.C. (0.37 kPa) 
may cause rough starting, noisy combustion or nuisance outages. 
Increases  or  spikes  in  static  pressure  during  off  cycles  may 
cause failure to ignite or in severe cases damage to appliance 
gas valves. If your low pressure system does nOT meet these 
requirements, the installer is responsible for the corrections.
High Pressure building supply systems use pressures that exceed 
14” W.C. (3.49 kPa) (1/2 PSI Gauge). These systems must use 
field supplied regulators to lower the gas pressure to less than 
14” W.C. (3.49 kPa) (1/2 PSI Gauge). Appliances require gas 
regulators that are properly sized for the water heater input and 
deliver the rating plate specified pressures. Gas supply systems 
where pressure exceeds 5 PSI (34.5 kPa) often require multiple 
regulators  to  achieve  desired  pressures.  Systems  in  excess 
of 5 PSI building pressure should be designed by gas delivery 
professionals for best performance. Water heaters connected to 
gas supply systems that exceed 14” W.C. (3.49 kPa) (1/2 PSI 
Gauge) at any time must be equipped with a gas supply regulator.
gas pressure reQuirements
All models require a minimum gas supply pressure of 3.5” W.C. 
(0.87 kPa) The minimum supply pressure is measured while gas 
is  flowing  (dynamic  pressure).  The  supply  pressure  (dynamic) 
should never fall below 3.5” W.C. (0.87 kPa) The supply pressure 
should be measured with all gas fired appliances connected to 
the common main firing at full capacity. If the supply pressure 
drops more than 1.5” W.C. (0.37 kPa) as gas begins to flow to 
the water heater then the supply gas system including the gas 
line  and/or  the  gas  regulator  may  be  restricted  or  undersized. 
See  Supply  Gas  regulator  section  and  Gas  Piping  section  of 
this manual. 
The gas valve on all models has a maximum gas supply pressure 
limit of 14" W.C. (3.48 kPa). The maximum supply pressure is 
measured while gas is not flowing (static pressure).
supply gas regulator
The  maximum  allowable  gas  supply  pressure  for  this  water 
heater is 14 inches W.C. (3.48 kPa). Install a positive lock-up gas 
pressure regulator in the gas supply line if inlet gas pressure can 
exceed 14 inches W.C. (3.48 kPa) at any time. regulators must 
be sized/used according to manufacturer's specifications.
If a positive lock-up regulator is required follow these instructions:
1.  Positive lock-up gas pressure regulators must be rated at or 
above the input btu/hr rating of the water heater they supply.
2.  Positive  lock-up  gas  pressure  regulator(s)  should  be 
installed no closer than 3 feet (1 meter) and no farther than 8 
feet (2.4 meters) of equivalent length from the water heater’s 
inlet gas connection.
3.  After installing the positive lock-up gas pressure regulator(s) 
an initial nominal supply pressure setting of 7.0” W.C. (1.74 
kPa)  while  the  water  heater  is  operating  is  recommended 
and  will  generally  provide  good  water  heater  operation. 
Some addition adjustment maybe required later to maintain 
a steady gas supply pressure.
installation reQuirements