Compressor Check Flow Chart
Compressor Fault
Check maintenance 
display
Put unit in stand by 
Wait eight (8) minutes 
for compressor time 
out
Turn power off at 
breaker / fuse panel
Verify connections 
and insure they are 
seated fully
Check 
Compressor 
shell temperature
Allow compressor to 
cool; thermal switch 
to reset
Restore power at 
breaker / fuse panel-
press power button 
and verify that unit is 
in effi ciency mode
Raise set 
point 10°
Wait ten (10) seconds 
for compressor to 
turn on
Perform voltage and 
current checks
Fan 
on
Hot
Cool
No
Fan 
on
No
Yes
Yes
Table 4
Check
Voltage *
(VAC)
± 5%
Resistance
(Ω)
± 5%
C-R
240
3.5
C-S
298
6.1
R-S
380
9.5
C-GROUND
128
>1M
R-GROUND
112
>1M
S-GROUND
321
>1M
*Values with 240 VAC input
Check CN207 on 
control board pin 
1 to 3 for 240 VAC
Voltage 
present
No
Yes
Replace 
control board *
Replace fan 
assembly
*If replacing the control board does not resolve the issue, contact technical support.