American Water Heater STCE3-52/80/119 ユーザーズマニュアル

ページ / 76
Servicing should only be performed by a Qualified Service Agent
17
OPERATION & SERVICE
FUSES
The water heaters covered in this manual have power circuit fuses to protect the heating 
element circuits. Electronic Control models will have two additional fuses to protect the 
primary winding of the 120 Volt Control Circuit Transformer. See Figures 1 and 2 on pages 8 
and 9 for location. Testing fuses requires an ohm meter, an AC volt meter and an insulated 
fuse puller - see Tools Required page 3.
Service Note - Replacement Fuses: Replacement power circuit fuses MUST BE of the 
same value and type as the factory installed fuses - Class G/SC-30 Amp/Time Delay. 
Replacement 120 Volt Control Circuit Transformer fuses MUST BE of the same value and 
type as the factory installed fuses - Class G/SC-3 Amp.
Ohm Meter Method
1 Secure power to the water heater at the main breaker or disconnect switch.
2 Remove each fuse to be tested with an insulated fuse puller.
3 Set the Ohm meter to it’s lowest resistance range (< 200) or to an audible beep continuity test setting if 
so equipped.
4 Touch the meter probes to both ends of each fuse simultaneously. 
5 If the fuse being tested shows a low resistance (< 1 ohms) or the continuity test feature sounds an 
audible beep the fuse being tested is good and can be re-installed.
6 If the fuse being tested shows infinite resistance (open circuit) or the continuity test feature does not 
sound an audible beep the fuse being tested is blown and must be replaced.
Volt Meter Method
Fuses can also be checked using an AC volt meter. The power supply must be turned on 
and a call for heat must be active (all thermostats/contactors must be closed) during this 
test. Touch the two test probes to both ends of all fuses while still in their fuse blocks.
• A high voltage (at or above 120 VAC) reading indicates the fuse is blown.
• A zero volt reading generally indicates the fuse is good. Next check for voltage between each end of the fuse 
and ground to ensure voltage is present at both ends of the fuse. If no voltage is present between either end 
of the fuse and ground the test has not been conclusive - secure power to the water heater and perform the 
ohm meter test method described above.
The voltage test method is a good way to quickly identify fuses that are blown but it is not 
always conclusive due to the dependence on power being present at both ends of the fuse, 
the switch contacts in thermostats/contactors being closed and correct wiring. Keep this in 
mind as there may be times when a fuse that is blown tests good due to one of these 
dependencies not being met. The ohm meter method described above is 100% conclusive.
Volt Meter Method
Ohm Meter Method