ELECTRONIC CONTROL SYSTEM
Servicing should only be performed by a Qualified Service Agent
52
TEMPERATURES MENU
Operating Set Point
User adjustable setting 90°F to 190°F range; 
factory default is 120°F. When the water 
temperature sensed by the control system 
from the immersion Temperature Probe 
reaches the Operating Set Point the control 
system will end the heating cycle. A call for 
heat will be activated again when the water 
temperature drops below the Operating Set 
Point minus the 1st Differential Setting. 
ExampleOperating Set Point is 120°F, the 1st Differential Setting is 2°F (factory default). A 
call for heat will be activated when the sensed water temperature drops to 118°F.
Differential Settings
Adjustable user setting(s) 1°F to 20° range; factory default is 2°F. The water heaters covered 
in this manual will have 3, 6 or 9 heating elements. Each group of 3 heating elements is one 
“Bank” of heating elements. Heating elements are energized in Banks of 3. Each Bank of 
heating elements will have a Differential Setting associated with it. Differential Settings are 
located in the Temperatures Menu.
There is a 1st Differential Setting on all models. There will be one additional Differential 
Setting visible/adjustable for each additional Bank of (3) heating elements.
Operating Sequence: With an Operating Set Point of 120°F and all Differential settings at 
2°F the On/Off sequencing of heating element Banks would be as follows:
Tank Temperature
Non adjustable information display. Current water temperature as sensed by the control 
system from the immersion Temperature Probe.
Tank Probe Offset
User adjustable setting -5°F to +5°F range; factory default is 0°F. If the current Tank 
Temperature is sensed (from the immersion Temperature Probe) at 120°F and the offset is 
adjusted to -5°F the control system would calibrate or “offset” the Tank Temperature to 
115°F. Heating cycles would then start/stop based on the calibrated Tank Temperature.
Used to calibrate for slight differences in control system temperature sensing. This can 
improve the precision of temperature control in the storage tank and at points of use. This 
feature can also be used to compensate for building recirculation loops (hot water returning 
to the storage tank) that may cause the heating cycle to terminate prematurely.
BANK NUMBER
DIFFERENTIAL SETTING
TURN ON TEMP
TURN OFF TEMP
Bank 1
2°F
118°F
120°F
Bank 2
2°F
116°F
118°F
Bank 3
2°F
114°F
116°F