Servicing should only be performed by a Qualifi ed Service Agent
INSTALLATION CONSIDERATIONS
Table 2
MINIMUM CLEARANCES TO COMBUSTIBLE SURFACES
“A” - Right Side
“B” - Left Side
“C” - Back
5” (12.7 cm)
5” (12.7 cm)
5” (12.7 cm)
A, B, and C clearances to non-combustible surfaces is “0” inches.  A 20” clearance to cover remains unchanged. 
CLEARANCES (EXTERIOR)
The illustration below shows the required clearances for venting units using natural draft venting.  
The vent must extend at least 3 feet above the highest point where it passes through a 
roof of a building and at least 2 feet higher than any portion of a building within a horizontal 
distance of 10 feet (for vents of 12 inches in diameter or less).      
Reference: NFPA 54 ANSI Z 223.1.
Figure 6