Mastic 91P ユーザーズマニュアル

ページ / 42
20                                                                                                                                                       
L100001                                                                                                                                                                            
21
•     If a 90° elbow is used in the horizontal vent run (level height 
maintained) the horizontal vent length is reduced by 36" (914 
mm) (Fig. 
20
 A and B) This does not apply if the 90° elbows 
are used to increase or redirect a vertical rise. See Figure 19.
Example: According to the vent graph (page 16) the maximum 
horizontal vent length in a system with a 7.5' vertical rise is 15’ 
(6m) and if a 90° elbow is required in the horizontal vent it must 
be reduced to 12'. 
In Figures 20 and 21, Dimension A plus B must not be greater 
than 17' (5.2m).
•     The maximum number of 45° elbows permitted per side wall 
installation is two (2). These elbows can be installed in either 
the vertical or horizontal run. 
•     For each 45° elbow installed in the horizontal run, the length 
of the horizontal run MUST be reduced by 18" (45cm). This 
does not apply if the 45° elbows are installed on the vertical 
part of the vent system.
•     The maximum number of elbow degrees in a system is 270°. 
See Figure 22.
Figure 21 - Maximum Vent Run with Elbows
Figure 20 - Maximum Vent Run  with Elbows
Figure 22 - Maximum Elbow Usage 
VENT INSTALLATION 
1 + 2 + 3 + 4 = 270°
1
2
3
1
2
3
4
HORIZONTAL TERMINATION CONFIGURATION — 
RIGID VENTING 
(Continued)
Example: 
Elbow 1   =   90°
 
Elbow 2   =   45°
 
Elbow 3   =   45°
 
Elbow 4   =   90°
Total Angular Variation  
=   270°
7'6"
10'
7'
A
B
90° Elbow reduces horizontal 
run allowed by 3'.
 
 
A+B=17' Maximum.