Franklin 2007 ユーザーズマニュアル

ページ / 75
Application – Single-Phase Motors
75 °C
2 or 3-Wire Cable, 60 Hz (Service Entrance to Motor - Maximum Length In Feet)
Lengths in BOLD only meet the US National Electrical 
Code ampacity requirements for individual conductors 
60 °C or 75 °C in free air or water, not in magnetic 
enclosures, conduit or direct buried.
Lengths NOT in bold meet the NEC ampacity 
requirements for either individual conductors or jacketed 
60 °C or 75 °C cable and can be in conduit or direct 
buried. Flat molded and web/ribbon cable are considered 
jacketed cable.
If any other cable is used, the NEC and local codes 
should be observed.
Cable lengths in tables 11 & 11A allow for a 5% voltage 
drop running at maximum nameplate amperes. If 3% 
voltage drop is desired, multiply table 11 and 11A lengths 
by 0.6 to get maximum cable length.
The portion of the total cable length, which is between 
the supply and single-phase control box with a line 
contactor, should not exceed 25% of total maximum 
allowable to ensure reliable contactor operation. Single-
phase control boxes without line contactors may be 
connected at any point in the total cable length.
Tables 11 & 11A are based on copper wire. If aluminum 
wire is used, it must be two sizes larger than copper wire 
and oxidation inhibitors must be used on connections. 
EXAMPLE: If tables 11 & 11A call for #12 copper wire, 
#10 aluminum wire would be required.
Contact Franklin Electric for 90 °C cable lengths. See 
pages 15, 48, and 49 for applications using 230 V motors 
on 208 V power systems.
MOTOR RATING 
60 °C INSULATION - AWG COPPER WIRE SIZE
VOLTS
HP
KW
14
12
10
8
6
4
3
2
1
0
00
000
0000
115
1/2
.37
100
160
250
390
620
960
1190
1460
1780
2160
2630
3140
3770
230
1/2
.37
400
650
1020
1610
2510
3880
4810
5880
7170
8720
3/4
.55
300
480
760
1200
1870
2890
3580
4370
5330
6470
7870
1
.75
250
400
630
990
1540
2380
2960
3610
4410
5360
6520
1.5
1.1
190
310
480
770
1200
1870
2320
2850
3500
4280
5240
2
1.5
150
250
390
620
970
1530
1910
2360
2930
3620
4480
3
2.2
120
190
300
470
750
1190
1490
1850
2320
2890
3610
5
3.7
0
0
180
280
450
710
890
1110
1390
1740
2170
2680
7.5
5.5
0
0
0
200
310
490
610
750
930
1140
1410
1720
10
7.5
0
0
0
0
250
390
490
600
750
930
1160
1430
1760
15
11
0
0
0
0
170
270
340
430
530
660
820
1020
1260
Table 11
MOTOR RATING 
75 °C INSULATION - AWG COPPER WIRE SIZE
VOLTS
HP
KW
14
12
10
8
6
4
3
2
1
0
00
000
0000
115
1/2
.37
100
160
250
390
620
960
1190
1460
1780
2160
2630
3140
3770
230
1/2
.37
400
650
1020
1610
2510
3880
4810
5880
7170
8720
3/4
.55
300
480
760
1200
1870
2890
3580
4370
5330
6470
7870
9380
1
.75
250
400
630
990
1540
2380
2960
3610
4410
5360
6520
7780
9350
1.5
1.1
190
310
480
770
1200
1870
2320
2850
3500
4280
5240
6300
7620
2
1.5
150
250
390
620
970
1530
1910
2360
2930
3620
4480
5470
6700
3
2.2
120
190
300
470
750
1190
1490
1850
2320
2890
3610
4470
5550
5
3.7
0
110
180
280
450
710
890
1110
1390
1740
2170
2680
3330
7.5
5.5
0
0
120
200
310
490
610
750
930
1140
1410
1720
2100
10
7.5
0
0
0
160
250
390
490
600
750
930
1160
1430
1760
15
11
0
0
0
0
170
270
340
430
530
660
820
1020
1260
Table 11A
1 Foot = .3048 Meter
11
60 °C