Application – Three-Phase Motors
Footnotes for Tables 28, 29, and 30 
NOTE 1: Furnas intermediate sizes between 
NEMA starter sizes apply where (1) is shown in 
tables, size 1.75 replacing 2, 2.5 replacing 3, 3.5 
replacing 4, and 4.5 replacing 5. Heaters were 
selected from Catalog 294, table 332 and table 
632 (starter size 00, size B). Size 4 starters are 
heater type 4 (JG). Starters using these heater 
tables include classes 14, 17 and 18 (inNOVA), 
classes 36 and 37 (reduced voltage), and classes 
87, 88 and 89 (pump and motor control centers). 
Overload relay adjustments should be set no 
higher than 100% unless necessary to stop 
nuisance tripping with measured amps in all lines 
below nameplate maximum. Heater selections for 
class 16 starters (Magnetic Defi nite Purpose) will 
be furnished upon request.
NOTE 2: General Electric heaters are type CR123 
usable only on type CR124 overload relays and 
were selected from Catalog GEP-126OJ, page 
184. Adjustment should be set no higher than 
100%, unless necessary to stop nuisance tripping 
with measured amps in all lines below nameplate 
maximum.
NOTE 3: Adjustable overload relay amp settings 
apply to approved types listed. Relay adjustment 
should be set at the specifi ed SET amps. Only if 
tripping occurs with amps in all lines measured to 
be within nameplate maximum amps should the 
setting be increased, not to exceed the MAX 
value shown.
NOTE 4: Heaters shown for ratings requiring 
NEMA size 5 or 6 starters are all used with 
current transformers per manufacturer standards. 
Adjustable relays may or may not use current 
transformers depending on design.
HP
KW
VOLTS
NEMA
STARTER
SIZE
HEATERS FOR
OVERLOAD RELAYS
ADJUSTABLE
RELAYS
(NOTE 3)
FURNAS
(NOTE 1)
G.E.
(NOTE 2)
SET
MAX.
5
3.7
200
1
K61
L220B
17.6
19.1
230
1
K61
L199B
15.4
16.6
380
0
K52
L122B
9.4
10.1
460
0
K49
L100B
7.7
8.3
575
0
K42
L825A
6.1
6.6
7.5
5.5
200
1
K67
L322B
26.3
28.3
230
1
K64
L293B
22.9
24.6
380
1
K57
L165B
13.9
14.9
460
1
K54
L147B
11.4
12.3
575
1
K52
L111B
9.1
9.8
10
7.5
200
2(1)
K72
L426B
34.4
37.0
230
2(1)
K70
L390B
29.9
32.2
380
1
K61
L220B
18.1
19.5
460
1
K58
L181B
15.0
16.1
575
1
K55
L147B
12.0
12.9
15
11
200
3(1)
K76
L650B
50.7
54.5
230
2
K75
L520B
44.1
47.4
380
2(1)
K68
L322B
26.7
28.7
460
2(1)
K64
L265B
22.0
23.7
575
2(1)
K61
L220B
17.7
19.0
20
15
200
3
K78
L787B
64.8
69.7
230
3(1)
K77
L710B
56.4
60.6
380
2
K72
L426B
34.1
36.7
460
2
K69
L352B
28.2
30.3
575
2
K64
L393B
22.7
24.4
25
18.5
200
3
K86
L107C
80.3
86.3
230
3
K83
L866B
69.8
75.0
380
2
K74
L520B
42.2
45.4
460
2
K72
L426B
34.9
37.5
575
2
K69
L352B
27.9
30.0
30
22
200
4(1)
K88
L126C
96.7
104.0
230
3
K87
L107C
84.1
90.4
380
3(1)
K76
L650B
50.9
54.7
460
3(1)
K74
L520B
42.0
45.2
575
3(1)
K72
L390B
33.7
36.2
40
30
380
3
K83
L866B
69.8
75.0
460
3
K77
L710B
57.7
62.0
575
3
K74
L593B
46.1
49.6
50
37
380
3
K87
L107C
86.7
93.2
460
3
K83
L950B
71.6
77.0
575
3
K77
L710B
57.3
61.6
60
45
380
4(1)
K89
L126C
102.5
110.2
460
4(1)
K87
L107C
84.6
91.0
575
4(1)
K78
L866B
67.7
72.8
Table 29 - 60 Hz  
6" 
 Motors
29