Franklin 2007 ユーザーズマニュアル

ページ / 75
Application – Three-Phase Motors
 1
50
= 0.02 or 2%
A full three-phase supply is recommended for all three-
phase motors, consisting of three individual transformers 
or one three-phase transformer. So-called “open” delta 
or wye connections using only two transformers can be 
used, but are more likely to cause problems, such as 
poor performance, overload tripping or early motor failure 
due to current unbalance.
Transformer rating should be no smaller than listed in 
table 4 for supply power to the motor alone.
1.   Established correct motor rotation by running in both 
directions. Change rotation by exchanging any two 
of the three motor leads. The rotation that gives the 
most water fl ow is always the correct rotation.
2.   After correct rotation has been established, check the 
current in each of the three motor leads and calculate 
the current unbalance as explained in 3 below.
  
If the current unbalance is 2% or less, leave the leads 
as connected.
 
If the current unbalance is more than 2%, current 
readings should be checked on each leg using each 
of three possible hook-ups. Roll the motor leads 
across the starter in the same direction to prevent 
motor reversal. 
3.   To calculate percent of current unbalance:
A.  Add the three line amps values together.
B.  Divide the sum by three, yielding average 
current.
C.  Pick the amp value which is furthest from the 
average current (either high or low).
D.  Determine the difference between this amp 
value (furthest from average) and the average.
E.  Divide the difference by the average. Multiply the 
result by 100 to determine percent of unbalance.
4.   Current unbalance should not exceed 5% at service  
factor load or 10% at rated input load. If the unbalance 
cannot be corrected by rolling leads, the source of 
the unbalance must be located and corrected. If, 
on the three possible hookups, the leg farthest from 
the average stays on the same power lead, most 
of the unbalance is coming from the power source. 
However, if the reading farthest from average moves 
with the same motor lead, the primary source of 
unbalance is on the “motor side” of the starter. In this 
instance, consider a damaged cable, leaking splice, 
poor connection, or faulty motor winding.
Checking and Correcting Rotation and Current Unbalance
T2
T1
T3
L1
L2
L3
T1
T3
T2
L1
L2
L3
T3
T2
T1
L1
L2
L3
1st Hook Up
2nd Hook Up
3rd Hook Up
supply
starter
motor
EXAMPLE:
  T1 = 51 amps 
T3 = 50 amps 
T2 = 50 amps 
T2 = 46 amps 
T1 = 49 amps 
T3 = 48 amps 
T3 = 53 amps 
T2 = 51 amps 
T1 = 52 amps
Total = 150 amps    Total = 150 amps   Total = 150 amps
+
+
+
50 - 46 = 4 amps 
50 - 49 = 1 amp 
50 - 48 = 2 amps
 2
50
= 0.04 or 4%
Phase designation of leads for CCW rotation viewing 
shaft end.
To reverse rotation, interchange any two leads.
Phase 1 or “A” - Black, T1, or U1
Phase 2 or “B” - Yellow, T2, or V1
Phase 3 or “C” - Red, T3, or W1
NOTICE: Phase 1, 2 and 3 may not be L1, L2 and L3.
FIG. 10 
FULL THREE-PHASE
FIG. 11 
OPEN DELTA
150
 
= 50
 
amps
150
 
= 50
 
amps
 4
50
= 0.08 or 8%
150
 
= 50
 
amps
Three-Phase Power Unbalance
33