26
Underload Smart Reset
If a motor Underload fault condition occurs, the most likely cause is an 
overpumped or dry well. To allow the well to recover, the SubDrive300 
controller will wait 30 seconds to 5 minutes, determined by duration of 
the previous run time, before restarting the motor. For example, the fi rst 
time the fault occurs, the controller will wait 30 seconds before attempting 
to restart the pump. If the system would then run for 1 minute and an 
Underload fault recurs, the controller will wait 4 minutes before attempting 
to restart the pump. This schedule allows for the minimum off-time possible 
based on the recovery time of the well.
Figure 5:  “Smart Reset” Well Recovery Time
Over-Temperature Foldback
The SubDrive300 controller is designed for full power operation in ambient 
temperatures up to 125°F (51°C) as long as the input voltage is kept at 230 
VAC. Under extreme thermal conditions, the controller will reduce output 
power in an attempt to avoid shutdown. Full pump output is restored when 
the controller temperature cools to a safe level.
0
6.0
5.0
4.0
3.0
2.0
1.0
0.0
1
2
3
4
5
6
7
8
Run Time  (Min.)
Off Time 
(Min.)