Siemens SR200R ユーザーズマニュアル
![Siemens](https://files.manualsbrain.com/attachments/fea10bc852adcb1f4f76708d5daebca542e532b9/common/fit/150/50/c53f5738b57089fc3d6c279e23db7450685a19c9616727fc1f659077967b/brand_logo.png)
6
5.
Let the generator stabilize and warm up at no-
load for at least five minutes.
load for at least five minutes.
6.
Set the generator's main circuit breaker (CB1) to
its ON or CLOSED position.
its ON or CLOSED position.
DANGER
PROCEED WITH CAUTION. GENERATOR
OUTPUT VOLTAGE IS NOW BEING DELIVERED
TO TRANSFER SWITCH TERMINALS. CONTACT
WITH LIVE TERMINALS RESULTS IN EXTREMELY
DANGEROUS AND POSSIBLY FATAL ELECTRICAL
SHOCK.
TO TRANSFER SWITCH TERMINALS. CONTACT
WITH LIVE TERMINALS RESULTS IN EXTREMELY
DANGEROUS AND POSSIBLY FATAL ELECTRICAL
SHOCK.
7.
With an accurate AC voltmeter and frequency
meter, check the no-load, voltage and frequency.
meter, check the no-load, voltage and frequency.
Single-phase generator supply:
Measure across ATS terminal lugs E1 to E2. Also
check E1 to NEUTRAL and E2 to NEUTRAL.
check E1 to NEUTRAL and E2 to NEUTRAL.
a. Frequency
....................................... 60-62
Hertz
b. Terminals E1 to E2 ........................ 240-246 VAC
c. Terminals E1 to NEUTRAL ............. 120-123 VAC
d. Terminals E2 to NEUTRAL ............. 120-123 VAC
c. Terminals E1 to NEUTRAL ............. 120-123 VAC
d. Terminals E2 to NEUTRAL ............. 120-123 VAC
8. Set the generator’s main circuit breaker (CB1) to
its OFF or OPEN position.
9. Set the AUTO/OFF/MANUAL switch to the OFF
position to shut down the generator.
NOTE:
Do NOT proceed until generator AC output volt-
age and frequency are correct and within stated
limits. If the no-load voltage is correct but no-
load frequency is incorrect, the engine governed
speed probably requires adjustment. If no-load
frequency is correct but voltage is not, the voltage
regulator may require adjustment.
age and frequency are correct and within stated
limits. If the no-load voltage is correct but no-
load frequency is incorrect, the engine governed
speed probably requires adjustment. If no-load
frequency is correct but voltage is not, the voltage
regulator may require adjustment.
3.4 GENERATOR TESTS UNDER LOAD
1. Set the generator's main circuit breaker to its
OFF or OPEN position.
2. Manually actuate the transfer switch main con-
tacts to their EMERGENCY (STANDBY) position.
Refer to the Manual Operation section.
Refer to the Manual Operation section.
3. To start the generator, set the AUTO/OFF/MANUAL
switch to MANUAL. When engine starts, let it sta-
bilize for a few minutes.
bilize for a few minutes.
4. Turn the generator's main circuit breaker to its
ON or CLOSED position. The generator now pow-
ers all LOAD circuits. Check generator operation
under load as follows:
ers all LOAD circuits. Check generator operation
under load as follows:
•
Turn ON electrical loads to the full rated watt-
age/amperage capacity of the generator. DO
NOT OVERLOAD.
age/amperage capacity of the generator. DO
NOT OVERLOAD.
•
With maximum rated load applied, check
voltage and frequency across transfer switch
terminals E1 and E2. Voltage should be
greater than 230 volts and frequency should
be greater than 59 Hertz.
voltage and frequency across transfer switch
terminals E1 and E2. Voltage should be
greater than 230 volts and frequency should
be greater than 59 Hertz.
•
Let the generator run under rated load for at
least 30 minutes. With unit running, listen for
unusual noises, vibration, overheating, etc.,
that might indicate a problem.
least 30 minutes. With unit running, listen for
unusual noises, vibration, overheating, etc.,
that might indicate a problem.
5.
When checkout under load is complete, set main
circuit breaker of the generator to its OFF or
OPEN position.
circuit breaker of the generator to its OFF or
OPEN position.
6.
Let the generator run at no-load for several min-
utes. Then, shut down by setting the AUTO/OFF/
MANUAL switch to its OFF position.
utes. Then, shut down by setting the AUTO/OFF/
MANUAL switch to its OFF position.
7.
Move the switch's main contacts back to their
UTILITY position. For example, load connected
to UTILITY power supply. Refer to the Manual
Operation section. Handle and operating lever of
transfer switch should be in UP position.
UTILITY position. For example, load connected
to UTILITY power supply. Refer to the Manual
Operation section. Handle and operating lever of
transfer switch should be in UP position.
8.
Turn on the UTILITY power supply to transfer
switch, using whatever means provided (such as
a UTILITY main line circuit breaker). The UTIL-
ITY power source now powers the loads.
switch, using whatever means provided (such as
a UTILITY main line circuit breaker). The UTIL-
ITY power source now powers the loads.
9. Set the generator's AUTO/OFF/MANUAL switch to
its AUTO position. The system is now set for fully
automatic operation.
automatic operation.
Section 3 — Operation
“HS” Type Transfer Switch