Mitsubishi Electronics QJ71DN91 ユーザーズマニュアル

ページ / 150
9 - 4                                                                                                                                                       9 - 4
MELSEC-Q
9   TROUBLESHOOTING
9.1.3 When communication with a specific slave node cannot be performed (using the
master function)
Communication with a specific slave node cannot be 
performed (when the NS LED is flashing in red)
Is the slave node power turned ON?
Is the communication cable securely 
connected to the slave node?
Are the parameters written?
Create and write correct parameters.
Take an action according to the error code.
Turn ON the slave node power.
Connect the communication cable securely.
Is the communication speed the 
same as that of other nodes?
Set the same communication speed as that of 
other nodes.
Are all node  numbers unique?
Set non-duplicate node numbers.
Is the slave node set in a parameter?
Is the actual node 
number the same as the node  number 
in a parameter?
Is a reserved node not set?
Does the specified 
connection type match with the slave 
node specification?
Do the UCMM presence 
and message group match with the slave 
node specification?
Does the setting value 
of the watchdog timeout action match with the 
slave node specification?
Does the I/O configuration 
in a parameter match with the I/O configuration of 
the actual slave node?
Is the production inhibit time not too short?
Is the production inhibit time not too long?
Is an error code generated?
Check the entire network status such as noise 
and installation.
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes