This Guide provides basic information about how 
to turn ON the analyzer and conduct a combustion 
efficiency test. Detailed information concerning 
the analyzer’s operation, set up, and calibration is 
contained in Instruction 24‑9428. 
Turning ON the Analyzer
1.  Place the probe tip in the area that contains 
the burner’s combustion‑air source. This 
step allows the analyzer to measure the 
combustion‑air temperature during the 
analyzer’s warm‑up period.
2.  Press analyzer’s I/O button. 
3.  Wait for the analyzer to complete its 
60 second warm‑up period. 
Performing a Combustion Test
4.  Press the  or  button to select the desired 
fuel and then press ENTER. The fuel codes are:
 
F1 = Natural Gas 
F3 = LPG
 
F2 = Oil #2 
F4 = Kerosene
             
 
    
 
Example: “F1” denotes 
Natural Gas
Sampling Locations
Insert the probe in the areas shown in the 
following illustrations to measure stack 
temperature, flue‑gas O
2
 content, and flue‑gas CO 
content (Model 60 only).
Water Trap / Filter Maintenance
Drain the water condensate collected in the water 
trap after every test.
Replace the filter element (P/N 07‑1644) when dirty.
Atmospheric Burner or 
Gravity Vented Forced Air
Hot Water 
Tank
Atmospheric or 
Gravity Vented 
Boiler 
80% Eff. Fan Assist 
or Power Vented 
Furnace/Boiler
90% Eff. 
Condensing 
Furnace/Boiler
Bacharach, Inc.
621 Hunt Valley Circle, New Kensington, PA 15068
Ph: 724-334-5000 • Fax: 724-334-5001 • Toll Free: 800-736-4666 
Website: www.bacharach-inc.com • E-mail: help@bacharach-inc.com
Printed in U.S.A. 
® Registered Trademark
WATER TRAP
CHAMBER
Pull apart using a slight
twisting motion
FILTER
CHAMBER
FILTER ELEMENT
Pry apart filter chamber using
a small flat-blade screwdriver
inserted into notch
“A”
“B”
When reassembling
the trap, make sure
that surfaces “A” and
“B” are in contact