Mitsubishi Electronics A951GOT ユーザーズマニュアル

ページ / 124
9.4 Troubleshooting in bus connection
9.4.1 Locating error positions
9 - 11
9
E
RROR CODES
 AND 
E
RROR ME
SSAGES
APPE
NDICES
INDEX
(3) Error messages appearing due to faulty Q/QnACPU bus connection and measure against errors
Error 
Code
Error 
Messages
Check Timing
Cause and check point
Error detail
Remedy
Correspond-
ing CPU
1310
I/O INT 
ERROR.
During interrupt
An imprecise interrupt occurs to the PLC 
CPU.
(1)  Check that the module and the 
cables are connected correctly.
(2)  Replace the faulty module and 
the cables with new ones.
(3)  Check that the PLC and the GOT 
are earthed correctly.
(4)  Check the number of extension 
stages and the I/O slot numbers.
QCPU
QnACPU
1401
SP. UNIT 
DOWN
At CPU power ON/
At reset/When intel-
ligent function mod-
ule is accessed.
ٛ
 There was no response from the intelli-
gent function module during initial com-
munications stage.
• The size of the buffer memory of the 
intelligent function module is abnormal.
QCPU
At CPU power ON/
At reset
At the time of initial communication, a 
response is not returned from the special 
function module (including the GOT).
QnACPU
1402
When an intelligent 
function module 
access instruction 
is executed.
The intelligent function module was 
accessed in the program, but there was 
no response.
QCPU
During execution of 
FROM/TO instruc-
tion set
The special function module was 
accessed during the execution of a 
FROM/TO instruction set, but there was 
no response.
QnACPU
1403
When an End 
instruction is exe-
cuted
ٛ
 There was no response from the intelli-
gent function module when the END 
instruction is executed.
• An error is detected at the intelligent 
function module.
QCPU
1411
CONTROL
_BUS 
ERR.
At CPU power ON
At the time of initial communication, an 
imprecise response is returned from the 
special function module (including the 
GOT).
(1)  Check that the module and the 
cables are connected correctly.
(2)  Because a faulty module cannot 
be located, remove the modules 
one by one until no 
CONTROL_BUS ERR. message 
appears to indicate the module 
where the error occurs.
(Because the modules are 
removed, SP. UNIT ERR. 
message may appear. Stop 
transmitting the FROM/TO 
instruction to the applicable 
module.)
QCPU
QnACPU
1412
During execution of 
FROM/TO instruc-
tion set
When the FROM/TO instruction is exe-
cuted, an imprecise response is returned 
from the special function module (includ-
ing the GOT).
Check the faulty module from the 
error step.
(1)  Check that the module and the 
cables are connected correctly.
(2)  Replace the faulty module with a  
new one.
(3)  Check that the PLC and the GOT 
are earthed correctly.
2000
UNIT VER-
IFY ERR.
When an End 
instruction is exe-
cuted
The information stored in the cards of the 
module installed in the base module and 
the communication module of the GOT is 
different from that read at the initial time.
(If an error occurs on a module (vacant) 
other than that installed in the base mod-
ule, the mis-operation may be caused by 
noise.)
Check the faulty module at special 
resisters SD1400 to SD1431.
(1)  Check that the module and the 
cables are connected correctly.
(2)  Check that the PLC and the GOT 
are earthed correctly.
QCPU