13. CHARACTERISTICS 
 
13.5 Inrush currents at power-on of main circuit and control circuit 
The following table indicates the inrush currents (reference value) that will flow when the maximum 
permissible voltage (253VAC) is applied at the power supply capacity of 2500kVA and the wiring length of 
1m. 
 
Inrush Currents (A
0-p
Servo Amplifier 
Main circuit power supply (L
1
, L
2
, L
3
Control circuit power supply (L
11
, L
21
MR-J2S-10CP 20CP 
30A (Attenuated to approx. 5A in 10ms) 
MR-J2S-40CP 60CP 
30A (Attenuated to approx. 5A in 10ms) 
MR-J2S-70CP 100CP 
54A (Attenuated to approx. 12A in 10ms) 
70 to 100A 
(Attenuated to approx. 0A in 0.5 to 1ms) 
MR-J2S-200CP 350CP 
120A (Attenuated to approx. 12A in 20ms) 
100 to 130A 
(Attenuated to approx. 0A in 0.5 to 1ms) 
MR-J2S-500CP 
44A (Attenuated to approx. 20A in 20ms) 
MR-J2S-700CP 
88A (Attenuated to approx. 20A in 20ms) 
30A 
(Attenuated to approx. 0A in several ms) 
MR-J2S-10CP1 20CP1 
59A (Attenuated to approx. 5A in 4ms) 
MR-J2S-40CP1 
72A (Attenuated to approx. 5A in 4ms) 
100 to 130A 
(Attenuated to approx. 0A in 0.5 to 1ms) 
 
Since large inrush currents flow in the power supplies, always use no-fuse breakers and magnetic 
contactors. (Refer to section 14.2.2.) 
When circuit protectors are used, it is recommended to use the inertia delay type that will not be tripped 
by an inrush current.