Mitsubishi Electronics MR-J3 ユーザーズマニュアル

ページ / 668
 
 
11 -  5 
11. TROUBLESHOOTING 
 
Display Name 
Definition 
Cause 
Action 
1. Faulty parts in the servo amplifier 
Checking method
Alarm (A15) occurs if power is 
switched on after disconnection 
of all cables but the control circuit 
power supply cables.
A15 Memory 
error 
(EEP-ROM) 
EEP-ROM fault 
2. The number of write times to EEP-
ROM exceeded 100,000. 
Change the servo amplifier. 
1. Encoder connector (CN2) 
disconnected. 
Connect correctly. 
2. Encoder fault 
Change the servo motor. 
3. Encoder cable faulty 
(Wire breakage or shorted) 
Repair or change the cable. 
A16 Encoder 
error 
(At power on) 
Communication error 
occurred between 
encoder and servo 
amplifier. 
4. Encoder cable type (2-wire, 4-wire) 
selection was wrong in parameter 
setting. 
Correct the setting in the fourth digit of 
parameter No.PC22. 
A17 Board 
error CPU/parts 
fault 
A19 Memory 
error 
(Flash ROM) 
ROM memory fault 
Faulty parts in the servo amplifier 
Checking method
Alarm (A17 or A19) occurs if 
power is switched on after 
disconnection of all cables but the 
control circuit power supply cable.
 
Change the servo amplifier. 
A1A Motor 
combination 
error 
Wrong combination 
of servo amplifier 
and servo motor. 
Wrong combination of servo amplifier 
and servo motor connected. 
Use correct combination. 
1. Encoder connector (CN2) 
disconnected. 
Connect correctly. 
2. Encoder cable faulty 
(Wire breakage or shorted) 
Repair or change the cable. 
A20 
Encoder error 2  Communication error 
occurred between 
encoder and servo 
amplifier. 
3. Encoder fault 
Change the servo motor. 
1. Power input wires and servo motor 
power wires are in contact. 
Connect correctly. 
2. Sheathes of servo motor power 
cables deteriorated, resulting in 
ground fault. 
Change the cable. 
A24 
Main circuit error  Ground fault 
occurred at the servo 
motor power (U,V 
and W phases) of 
the servo amplifier. 
3. Main circuit of servo amplifier failed. 
Checking method
Alarm (A24) occurs if the servo is
switched on after disconnecting
the U, V, W power cables from
the servo amplifier.
 
Change the servo amplifier. 
1. Voltage drop in encoder 
(Battery disconnected.) 
After leaving the alarm occurring for a few 
minutes, switch power off, then on again. 
Always make home position setting again. 
2. Battery voltage low 
Absolute position 
data in error 
3. Battery cable or battery is faulty. 
Change the battery.  
Always make home position setting again. 
A25 Absolute 
position erase 
Power was switched 
on for the first time in 
the absolute position 
detection system. 
4. Home position not set. 
After leaving the alarm occurring for a few 
minutes, switch power off, then on again. 
Always make home position setting again.