14. OPTIONS AND AUXILIARY EQUIPMENT 
 
Table 14.4 Servo motor’s leakage current example (Igm)
 
Table 14.5 Servo amplifier's leakage current example (Iga) 
 
 
Servo motor output [kW] 
Leakage current [mA] 
 
Servo amplifier capacity [kW]
Leakage current [mA] 
 
 
0.05 to 1 
0.1 
 
0.1 to 0.6 
0.1 
 
 
0.2 
 
0.75 to 3.5 (Note) 
0.15 
 
 
3.5 0.3 
 
5 7 2 
 
 
5 0.5 
 
11 15 5.5
 
 
 
7 0.7 
 
22 7
 
 
 
11 1.0 
 
 
 
15 1.3 
 
Note. For the 3.5kW of 400V class, leakage current is 2mA, 
which is the same as for 5kW and 7kW. 
 
 
22 2.3 
 
 
 
 
 
 
 
Table 14.6 Leakage circuit breaker selection example 
 
 
 
 
 
 
Servo amplifier 
Rated sensitivity current of leakage 
circuit breaker [mA] 
 
 
 
MR-J3-10T to MR-J3-350T 
MR-J3-10T1 to MR-J3-40T1 
MR-J3-60T4 to MR-J3-350T4 
15
 
 
MR-J3-500T(4) 30
 
 
MR-J3-700T(4) 50
 
 
 
 
MR-J3-11KT(4) to MR-J3-22KT(4) 
100
 
 
(2) Selection example 
Indicated below is an example of selecting a leakage current breaker under the following conditions. 
2mm
2    
5m
2mm
2    
5m
Ig1
Ig2
Servo
amplifier 
Iga
M
HF-KP43
Igm
NV
MR-J3-40T
 
Use a leakage current breaker generally available. 
Find the terms of Equation (14.1) from the diagram. 
 
Ig1 20
1000
5
0.1 [mA]
 
 
Ig2 20
1000
5
0.1 [mA]
 
 
Ign   0 (not used) 
 
Iga   0.1 [mA] 
 
Igm   0.1 [mA] 
 
Insert these values in Equation (14.1). 
 
Ig   10 {0.1 0 0.1 1 (0.1 0.1)} 
 
 4.0 [mA] 
 
According to the result of calculation, use a leakage current breaker having the rated sensitivity current (Ig) 
of 4.0[mA] or more. A leakage current breaker having Ig of 15[mA] is used with the NV-SP/SW/CP/CW/HW 
series.