15. COMMUNICATION FUNCTION 
 
15.5.10 Current alarm 
(1) Current alarm read 
Read the alarm No. which is occurring currently. 
 
(a) Transmission 
Send command [0][2] and data No. [0][0]. 
Command Data 
No. 
[0][2] [0][0] 
 
(b) Reply 
The slave station sends back the alarm currently occurring. 
0 0
Alarm No. is transferred in hexadecimal.
 
For example, "0032" means A32 and "00FF" means A_ _ (no alarm). 
 
(2) Read of the status display at alarm occurrence 
Read the status display data at alarm occurrence. When the data No. corresponding to the status display 
item is transmitted, the data value and data processing information are sent back. 
 
(a) Transmission 
Send command [3][5] and any of data No. [8][0] to [8][E] corresponding to the status display item to be 
read. Refer to section 15.4.1. 
 
(b) Reply 
The slave station sends back the requested status display data at alarm occurrence. 
0 0
Data 32 bits long (represented in hexadecimal)
(Data conversion into display type is required)
Display type
0: Conversion into decimal required
1: Used unchanged in hexadecimal
Decimal point position
0: No decimal point
1: Lower first digit (usually not used)
2: Lower second digit
3: Lower third digit
4: Lower fourth digit
5: Lower fifth digit
6: Lower sixth digit
 
(3) Current alarm clear 
As by the reset (RES) on, reset the servo amplifier alarm to make the servo amplifier ready to operate. After 
removing the cause of the alarm, reset the alarm with no command entered. 
Command Data 
No. 
Data 
[8][2] [0][0]  1EA5