Mitsubishi Electronics MR-J3 ユーザーズマニュアル

ページ / 668
 
 
16 -  101 
16. INDEXER POSITIONING OPERATION 
 
(2) Remedies for alarms 
 
CAUTION 
When any alarm has occurred, eliminate its cause, ensure safety, then reset the 
alarm, and restart operation. Otherwise, injury may occur. 
If an absolute position erase (A25) occurred, always make home position setting 
again. Not doing so may cause unexpected operation. 
As soon as an alarm occurs, turn off Servo-on (RYn0) and power off. 
 
POINT 
 
When any of the following alarms has occurred, do not deactivate the alarm 
and resume operation repeatedly. To do so will cause the servo 
amplifier/servo motor to fail. Remove the cause of occurrence, and leave a 
cooling time of more than 30 minutes before resuming operation. 
Regenerative error (A30) 
Overload 1 (A50) 
Overload 2 (A51) 
For the alarm deactivation method, refer to (1) in this section. 
 
When an alarm occurs, the trouble (ALM) switches off and the dynamic brake is operated to stop the servo 
motor. At this time, the display indicates the alarm No. 
The servo motor comes to a stop. Remove the cause of the alarm in accordance with this section. Use the 
MR Configurator to refer to a factor of alarm occurrence. 
 
Display Name 
Definition 
Cause 
Action 
1. Power supply voltage is low. 
2. There was an instantaneous control 
power failure of 60ms or longer. 
3. Shortage of power supply capacity 
caused the power supply voltage to 
drop at start, etc. 
4. The bus voltage dropped to the 
following value or less. 
MR-J3- T: 200VDC 
MR-J3- T1: 158VDC 
MR-J3- T4: 380VDC 
Check the power supply. 
A10 Undervoltage  Power 
supply 
voltage dropped. 
MR-J3- T:  
160VAC or less 
MR-J3- T1:  
83VAC or less 
MR-J3- T4: 
280VAC or less 
5. Faulty parts in the servo amplifier. 
Checking method
Alarm (A10) occurs if power is
switched on after disconnection 
of all cables but the control 
circuit power supply cables.
 
Change the servo amplifier. 
A12 
Memory error 1 
(RAM) 
RAM, memory fault 
A13 
Clock error 
Printed board fault 
Faulty parts in the servo amplifier. 
Checking method
Alarm (any of A12 and A13) 
occurs if power is switched on
after disconnection of all cables 
but the control circuit power 
supply cables.
 
Change the servo amplifier.