Lucent Technologies Release 6 ユーザーズマニュアル
DEFINITY Enterprise Communications Server Release 6
Installation and Test for Multi-Carrier Cabinets
Installation and Test for Multi-Carrier Cabinets
555-230-112
Issue 5
May 1998
Test the System
Page 4-3
Check Circuit Pack Configuration
4
Check Circuit Pack Configuration
1. Verify the screen displays:
Command:
2. Type list configuration all
and press
Enter
.
3. Verify the screen displays list configuration screens similar to the example
shown below. Check the report on the screen with the equipment installed
and make sure the software is communicating with each circuit pack
(except power supply circuit packs). Wait until after the diagnostic tests
later in this chapter before attempting to correct any problems.
and make sure the software is communicating with each circuit pack
(except power supply circuit packs). Wait until after the diagnostic tests
later in this chapter before attempting to correct any problems.
4. Note any circuit packs in the
VINTAGE
column stating:
BOARD NOT
PRESENT
or
CONFLICT
.
Screen 4-2.
Example System Configuration Screen
NOTE:
Under
Assigned Ports
, a “u” indicates unassigned ports and a number
indicates the port has been translated.