Black Box MPSH16-D20-120V ユーザーズマニュアル

ページ / 193
OUTLET MANAGED PDU
 
40
5.3.3.  Log Configuration
This feature allows you to create records of command activity, alarm actions and 
current and power consumption for the Outlet Managed PDU.  The Log features are 
enabled and configured via the System Parameters Menus.  The ability to view the 
Current and Power Metering logs is individually enabled for each account via the 
User Directory as described in Section 5.5.
•  Audit Log:  Creates a record of all power switching at the Outlet Managed 
PDU, including reboots and switching caused by Load Shedding, Load 
Shedding Recovery, Ping No Answer Reboots and Scheduled Reboots.  
Each Log record includes a description of the activity that caused the power 
switching, the username for the account that initiated the power switching or 
reboot and the time and date that the power switching or reboot occurred.  In 
addition to power switching activity, the Audit Log will also include login/
logout activity for each user account.
•  Alarm Log:  Creates a record of all Alarm Activity at the Outlet Managed 
PDU.  Each time an alarm is triggered, the Outlet Managed PDU will generate 
a record that lists the time and date of the alarm, the name of the Alarm that was 
triggered, and a description of the Alarm.
•  Current Metering Log:  Provides a record of current consumption.  Log 
records will include the time and date, current and voltage readings and 
temperature reading.  Current Metering Log data can be downloaded in ASCII, 
CSV or XML format.
5.3.3.1.  The Audit Log and Alarm Log
The System Parameters menu allows you to select three configuration options for 
the Audit Log and Alarm Log.  Note that the Audit Log and Alarm Log function 
independently, and parameters selected for one log will not be applied to the other.
•  Off:  Log is disabled, and command activity and/or alarm events are not logged.
•  On - With Syslog:  The Log is enabled, and power switching, reboot activity 
and/or alarm events will be logged.  The Outlet Managed PDU will generate a 
Syslog Message every time a Log record is created.
•  On - Without Syslog:  The Log is enabled, and power switching, reboot 
activity and/or alarm events will be logged, but the Outlet Managed PDU will 
not generate a Syslog Message every time a Log record is created.   
(Default Setting.)