installatiOn
CONNeCTiNg THe gROuNd
The nut and ground terminal on the generator should always 
be used to connect the generator to a suitable ground. The 
ground cable should be #8 size wire minimum.
At the generator, connect the terminal of the ground cable 
between the lock washer and the nut (Figure 2) and tighten 
the nut fully. Connect the other end of the ground cable to 
a suitable earth ground (ground rod).
GROUND ROD
FOR EARTH
GROUND
GENERATOR
GROUND LUG
CONNECT TO
BUILDING
GROUND
IF REQUIRED
8 FT. MINIMUM
REFERENCE
NEC 250-52(C)
GROUND
CABLE
#8 MINIMUM
240
V
120
ON
OFF
ON
OFF
GA-9.7HE
AC CIRCUIT
BREAKER
(for main)
15A
30A
30A
120V
240V
120/240V
START
BUTTON
OPERATION
SWITCH
IDLE CONTROL
SWITCH
for 120V
for 120V
20A
for 240V for 120/240V
AC CIRCUIT BREAKER
AC VOLTMETER
9700
OFF
OFF
35A
35A
Figure 2. Generator Grounding