page 18 — DCa300SSC / DCa300SSCU gen. • operation anD partS manUal — rev. #1 (08/10/11) 
generatOr cOntrOL paneL
Figure 4. Generator Control Panel
The definitions below describe the controls and functions 
of the Generator Control Panel (Figure 4).
1. 
pilot lamp — Indicates the system is running.
2. 
panel light — Normally used in dark areas or at night 
time. When activated, panel lights will illuminate. When 
the generator is not in use be sure to turn the panel 
light switch to the 
oFF position.
3. 
aC voltmeter — Indicates the output voltage present 
at the 
U,v, and W output terminal lugs.
4. 
auto on/off engine Controller (mpeC) —
 
This controller has a vertical row of status LED’s (inset), 
that when lit, indicate that an engine malfunction (fault) 
has been detected. When a fault 
has  been  detected  the  engine 
controller  will  evaluate  the  fault 
and all major faults will shutdown 
the  generator.  During 
cranking 
cycle, The MPEC will attempt to 
crank the engine for 10 seconds 
before disengaging.
 
If  the  engine  does  not  engage  (start)  by  the  third 
attempt, the engine will be shutdown by the engine 
controller’s 
over  Crank  protection  mode.  If  the 
engine engages at a speed (RPM’s) that is not safe, 
the controller will shutdown the engine by initializing 
the 
over Speed protection mode.
5. 
main Circuit Breaker  — This three-pole, 800 amp 
main breaker is provided to protect the 
U,v, and W 
output terminal lugs from overload.
6. 
voltmeter Change-over Switch — This switch allows 
the AC voltmeter to indicate phase to phase voltage 
between any two phases of the output terminals or to 
be switched off.
7. 
voltage regulator Control — Allows ±15% manual 
adjustment of the generator’s output voltage.
8. 
panel light Switch — When activated will turn on 
control panel light.
9. 
ammeter Change-over Switch — This switch allows 
the AC ammeter to indicate the current flowing to the load 
connected to any phase of the output terminals, or to be 
switched off. This switch does not effect the generator 
output in any fashion, it is for current reading only. 
10. 
AC Ammeter — Indicates the amount of current the 
load is drawing from the generator per leg selected by 
the ammeter phase-selector switch.
11. 
Frequency meter — Indicates the output frequency 
in hertz (Hz). Normally 60 Hz