generatOr start-up prOcedure 
BeFore STarTIng 
1.  Place the 
main, g.F.C.I., and aux. circuit breakers (Figure 
35) in the 
oFF position prior to starting the engine.
Figure 35. Main, Aux. and GFCI  
Circuit Breakers (OFF)
2.  Make sure the 
voltage change-over board has been 
configured for the desired output voltage.
3.  Connect the load to the 
receptacles or the output 
terminal  lugs  as  shown  in  Figure  11. These  load 
connection points can be found on the output terminal 
panel and the output terminal panel’s hard wire hookup 
panel. 
4.  Tighten terminal nuts securely to prevent load wires 
from slipping out.
5.  Close all engine enclosure doors (Figure 36).
Figure 36. Engine Enclosure Doors
  CaUTIon
The  engine’s  exhaust  contains  harmful  emissions. 
aLwaYS have adequate ventilation when operating. 
Direct exhaust away from nearby personnel.
  warnIng
never manually start the engine with the main, gFCI 
or auxiliary circuit breakers in the on (closed) position.
INCORRECT
CORRECT
STarTIng
1.  Place  the
  voltage  selector  switch  in  the  desired 
voltage position (Figure 37)..
Figure 37. Voltage Selector Switch
STarTIng (ManUaL)
1.  In warm weather conditions, skip to step 3. In cold 
weather conditions, preheat the engine glow plugs by 
turning  the  ignition  key  (Figure  38)  to  the 
rUn 
position..
Figure 38. Ignition Switch Pre-Heat 
(Run Position)
2.  Depending on the temperature of the coolant (cold 
weather conditions), the pre-heat lamp (Figure 39) will 
light (
on) and remain on until the pre-heating cycle has 
been completed. After completion of the pre-heating 
cycle, the light will go 
oFF and the engine will start up 
automatically.
Figure 39. Pre-Heat Lamp