DCA800SSK2 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #0 (09/03/09) — PAGE 37
GENERATOR SHUTDOWN PROCEDURES
NORMAL SHUTDOWN PROCEDURE
To shutdown the generator, use the following procedure:
Place the three 
1. 
auxiliary circuit breakers in the OFF 
position (Figure 36)
Place the engine speed switch (Figure 58) in the “LOW” 
2. 
(down) position.
Engine Speed Switch (Low)
Figure 58. 
Let the engine cool by running it at low speed for 3-5 
3. 
minutes with no load applied.
Place the 
4. 
MPEC Control Switch (Figure 59) to the 
OFF/RESET position.
MPEC Control Switch (Off/Reset)
Figure 59. 
Verify that 
5. 
all the status LEDs on the MPEC display 
are OFF (not lit).
Set the 
6. 
battery ON/OFF switch (Figure 60) to the 
"OFF" position.
Battery Switch (OFF)
Figure 60. 
Remove all loads from the generator.
7. 
Inspect entire generator for any damage or loosening 
8. 
of components that may have occurred during 
operation.
EMERGENCY SHUTDOWN PROCEDURE
To stop the engine in the event of an emergency, 
1. 
PUSH 
the emergency stop button (Figure 61) inward. This 
button is located on the engine operating panel, see 
Figure 5.
Emergency Stop Button
Figure 61.