page 34 — DCa25Usi 60 hz generaTor • operaTion anD parTs manUal — rev. #3 (07/19/11) 
generatOr shut-dOWn prOcedures
emergenCY shUTDoWn proCeDUre
1.  Place the 
main, g.F.C.i., and aux. circuit breakers (Figure 
52) in the 
oFF position.
2.  Turn the ignition key (Figure 52) to the
 sTop position.
Figure 52. Ingition Switch (Emergency)
normal shUTDoWn proCeDUre
To shutdown the generator, use the following procedure:
1.  Place both the 
main, gFCi and loaD circuit breakers 
as shown in Figure 50 to the 
oFF position..
Figure 50. Main, GFCI and Load 
Circuit Breakers Off
2.  Let the engine cool by running it at low speed for 3-5 
minutes with no load applied.
3.  Place  the  ignition  switch  (Figure  51)  in  the “
sTop” 
position, remove the key and store in a safe place. 
Figure 51. Ingition (Switch Normal)
4.  Verify that 
all status LEDs on the MPEC display are 
oFF (not lit). 
5.  Remove all loads from the generator.
6.  Inspect entire generator for any damage or loosening of 
components that may have occurred during operation.
  Warning
never  stop  the  engine  suddenly  except  in  an 
emergency.