page 26 — DCa125USI3CaN 60 hz geNerator • operatIoN aND partS maNUal — rev. #2 (09/24/13) 
gENErAtOr OUtPUtS
geNerator oUtpUt voltageS 
A wide range of voltages are available to supply voltage for 
many different applications. Voltages are selected by using 
the 
voltage selector switch (Figure 13). To obtain some of 
the voltages as listed in Table 7 (see below) will require a 
fine adjustment using the 
voltage regulator (VR) control 
knob located on the control panel. 
Voltage Selector Switch
The voltage selector switch (Figure 13) is located above 
the output terminal panel’s Hard Wire Hook-up Panel.  It 
has been provided for ease of voltage selection.
Figure 13. Voltage Selector Switch
Voltage Selector Switch Locking Button
To lock the voltage selector switch, 
press and hold the 
red button located at the bottom of the switch. While 
holding the red button down, insert a pad lock into the hole 
next to the button to retain it in the inward locked position. 
When the lock is removed, the red button is spring loaded 
and will return to its normal outward unlocked position.
  CAUTION
Never change the position of the voltage selector 
switch while the engine is running. alWaYS place 
circuit breaker in the 
OFF position before selecting 
voltage
.
table 7. voltages available
UvWo output 
terminal lugs
voltage Selector Switch
3-phase 240/139v position
voltage Selector Switch
3-phase 480/270v position
 
line-line
208V
220V
240V
416V
440V
480V
1Ø 
line-Neutral
120V
127V
139V
240V
254V
277V
voltage Selector Switch Single-phase 240/120v position
1Ø 
line-Neutral/
line-line
120V 
Line-Neutral
N/A
N/A
240V 
Line-Line
N/A
N/A
Generator Amperage
Table 8 shows the 
maximum amps the generator can 
provide. 
DO NOT exceed the maximum amps as listed..
GFCI Receptacle Load Capability
The load capability of the GFCI receptacles is directly 
related to the voltage being supplied at either the output 
terminals or the 2 twist lock auxiliary receptacles.
Table 9 and Table 10 show what amount of current is 
available at the GFCI receptacles when the output terminals 
and twist lock receptacles are in use. Be careful that your 
load does not to exceed the available current capability at 
the receptacles.
table 8. generator maximum amps
rated voltage
maximum amps
1Ø 120 Volt
277.8 amps (4 wire) 
301A x 2 (Zigzag)
1Ø 240 Volt
138.9 amps (4 wire) 
301A (Zigzag)
3Ø 240 Volt
301 amps
3Ø 480 Volt
150 amps
table 9.  1Ø gFCI receptacle load Capacity
KW in use 
twist lock (C6369)
available load 
Current (amps)
1Ø 240/120V
GFCI Duplex 
5-20R 120V
72.0
0 amps/receptacle
70.8
5 amps/receptacle
69.6
10 amps/receptacle
68.4
15 amps/receptacle
67.2
20 amps/receptacle
table 10.  3Ø gFCI receptacle load Capacity
Kva in Use 
(UvWo terminals)
available load 
Current (amps)
3Ø 240/480V
GFCI Duplex 
5-20R 120V
125
0 amps/receptacle
121
5 amps/receptacle
117
10 amps/receptacle
113
15 amps/receptacle
108
20 amps/receptacle