Mitsubishi 6CP-L50V18 ユーザーズマニュアル
MITSUBISHI MGS SERIES
DIESEL GENERATOR SET
60Hz/1800 rpm/380V
60Hz/1800 rpm/380V
MGS1400C (1/4)
POWER RATING (0.8 P.F.)
MODEL CODE
PRIME
1220 kW
6CP-L50V18
The photograph is MGS2000B
Voltage Variation
■ Standard Voltage
3Phase 4 Wires
380V
■ Voltages Available
3Phase 4 Wires
400 and 380V
Note:
Outputs for optional voltages may differ from standard output mentioned above.
CONDITIONS & DEFINITIONS
Prime【PRP】: Code:CP
Applicable for supplying power with varying load instead of the utility for an unlimited time. +10% overload is allowed in
accordance with ISO3046/1. Prime power in accordance with ISO15550,ISO3046/1,JIS8002-1,DIN6271 and BS5514.
Prime power in accordance with ISO8528.
accordance with ISO3046/1. Prime power in accordance with ISO15550,ISO3046/1,JIS8002-1,DIN6271 and BS5514.
Prime power in accordance with ISO8528.
Conditions:
Engine ratings are based on SAE J1349 standard conditions. These ratings also apply at ISO3046/1, DIN6271 and
BS5514 standard conditions.
Fuel rates are based on fuel oil of 35° API (16°C or 60° F) gravity having a LHV of 42,780 kJ/kg (18,390 Btu/lb.)
when used at 29°C (85° F) and weighing 838.9 g/liter (7.001lbs./U.S. gal.).
Note: * Please consult with your nearest Mitsubishi MGS dealer for overload and additional rating requirements.
BS5514 standard conditions.
Fuel rates are based on fuel oil of 35° API (16°C or 60° F) gravity having a LHV of 42,780 kJ/kg (18,390 Btu/lb.)
when used at 29°C (85° F) and weighing 838.9 g/liter (7.001lbs./U.S. gal.).
Note: * Please consult with your nearest Mitsubishi MGS dealer for overload and additional rating requirements.
DIMENSION (Reference Data)
Overall dimensions
L : Length
mm
4655
W : Width
mm
2160
H : Height
mm
2585
Total Weight (Dry)
kg
10640
Total Weight (Wet)
kg
11200
M
M
G
G
S
S
1
1
4
4
0
0
0
0
C
C
PRIME
1220 kW