DCA-125SSJU SERIES (STANDARD)— PARTS AND OPERATION  MANUAL— REV. #4  (06/03/03) — PAGE 45
DCA-125SSJU SERIES — GENERATOR START-UP PROCEDURE (AUTO MODE)
Before connecting this
generator to any
building’s electrical
system, a licensed
electrician
 must install
an 
isolation (transfer)
switch. Serious injury or death may result without this
transfer switch.
DANGER:
28. Perform steps 20 through 22 in the 
Before Starting
section (page 44) as outlined in the 
Manual Starting
Procedure.
29. Set the engine speed switch (Figure 69) to the “HIGH
position.
31. Continue to follow the steps outlined in the “
Manual
Start-up” procedure (start at step 11, page 42).
Figure 69. Engine Speed Switch (High)
When running the generator in the “AUTO
mode, remember the generator can start up
at any time without warning. NEVER attempt
to perform any maintenance when the
generator is in the auto mode.
WARNING:
When connecting the generator to a
isolation (transfer) switch, ALWAYS have
power applied to the generator's internal
battery charger. This will ensure that the
engine will not fail due to a dead battery.
CAUTION:
Figure 70.  Off/Manual Auto Switch (AUTO)
30. Place the Off/Manual/Auto switch (Figure 70) in the
AUTO position .
NOTE
When the generator is set in the
AUTO” mode, the generator will
automically start in the event  of
comercial power falling below a
prescribed level by means of a
contact closure that is generated
automatically by a transfer switch.
The 
Engine Speed Switch must be set
to the “HIGH” position when running in the
Auto-Start mode. Failing to set the switch
in the proper position can result in damage
to your generator when it turns on.
CAUTION: