Multiquip DCA-600SSV ユーザーズマニュアル

ページ / 108
DCA-600SSV — OPERATION AND PARTS MANUAL — REV. #0  (07/13/09) — PAGE 31
DCA-600SSV — GENERATOR OUTPUTS/GAUGE READING
How to Read the AC Ammeter and AC Voltage Gauges.
The AC ammeter and AC voltmeter gauges are controlled
by the Ac ammeter and AC voltmeter change-over switches.
Both of these switches are located on the generator control
panel and DO NOT effect the generator output. They are
provided to help observe how much power is being supplied,
produced at the UVWO terminals lugs.
Before taking a reading from either gauge, configure the volt-
age change-over board which produces the desired
outputvoltage. When the voltage change-over board is
jumpered for  
3Ø, 
240V operation (See Figure 15).
The 
ammeter and voltmeter
gauges  will only show a reading
when the 
Output Terminal
Lugs are connected to a load
and in use.
NOTE
Figure 15.  Voltage Change-Over Board
                             240V/3Ø Configuration
Figure 17  AC Voltmeter
Gauge
(Volt reading on W-U Lug)
Figure 16.  AC Voltmeter
Change-Over Switch
A
0
40
60
75
20
Figure 19.  AC Ammeter
(Amp reading on U lug)
Figure 18.  AC Ammeter
Change-Over Switch
AC Voltmeter Gauge Reading
Place the 
AC  Voltmeter Change-Over Switch (Figure 16)
in the W-U position and observe the phase to phase voltage
reading between the W and U terminals as indicated in the
AC  Voltmeter Gauge (Figure 17).
AC Ammeter Gauge Reading
Place the 
AC  Ammeter Change-Over Switch (Figure 18)
in the U position and observe the current reading (load drain)
on the U terminal as indicated in the 
AC  Ammeter Gauge
(Figure 19). This process can be repeated for terminals V
and W.