c.  When de-energized, the relay’s normally open 
contacts  are  open  and  its  normally-closed 
contacts are closed. 
d.  The  normally-closed  relay  contacts  will  deliver 
utility  source  power  to  the  utility  closing  circuit 
of the transfer mechanism. 
e.  The  normally  open  relay  contacts  will  deliver 
standby  source  power  to  the  transfer  mecha-
nism’s standby closing circuit. 
1
6
9
7
A
B
23
194
N1A
E1
126
205
Figure 5. Transfer Relay Schematic
2.  During automatic system operation, when the genera-
tor  circuit  board  “senses”  that  utility  source  voltage 
has dropped out, the circuit board will initiate engine 
cranking and startup.
3.  When  the  circuit  board “senses”  that  the  engine  has 
started, an “engine warm-up timer” on the circuit board 
starts timing.
4.  When the “engine warm-up timer” has timed out, 
circuit
 
board action completes the Wire 23 circuit to ground. 
a.  The transfer relay then energizes.
b.  The  relay’s  normally-closed  contacts  open  and 
its normally open contacts close. 
c.  When the normally open contacts close, standby 
source power is delivered to the standby closing 
coil and transfer to “Standby” occurs.
5.  When  the  generator  circuit  board “senses”  that  utility 
source voltage has been restored above a preset level, 
the board will open the Wire 23 circuit to ground.
a.  The transfer relay will de-energize, its normally- 
closed contacts will close and its normally open 
contacts will open.
b.  When the normally-closed relay contacts close, 
utility  source  voltage  is  delivered  to  the  utility 
closing coil to energize that coil.
c.  Retransfer back to UTILITY occurs.
neutral luG
The  standby  generator  is  equipped  with  an 
UNGROUNDED neutral. The neutral lug in the transfer 
switch is isolated from the switch enclosure.
manual tranSFer handle 
The manual transfer handle is retained in the transfer 
switch  enclosure  by  means  of  a  wing  stud.  Use  the 
handle  to  manually  actuate  the  transfer  mechanism 
load  contacts  to  either  the  UTILITY  or  STANDBY 
source side. 
Instructions  on  use  of  the  manual  transfer  handle 
may  be  found  in  Part  5,  “Operational  Tests  and 
Adjustments”.
terminal Block 
During  system  installation,  this  3-point  terminal  block 
must  be  properly  interconnected  with  an  identically 
labeled  terminal  block  in  the  generator  control  panel 
assembly.
0
15B
23
Figure 6. Transfer Switch Terminal Block
Terminals used on the terminal block are identified as 
0, 15B and 23.
UTILITY N1 AND N2:
Interconnect  with  identically  labeled  terminals  in  the 
generator  control  panel  assembly.  This  is  the  utility 
voltage signal to the circuit board. The signal is deliv-
ered to a step-down transformer in the control module 
assembly  and  the  resultant  reduced  voltage  is  then 
delivered to the circuit board. Utility 1 and 2 power is 
used by the circuit board as follows:
•  If  utility  source  voltage  should  drop  below  a  pre
-
set  level,  circuit  board  action  will  initiate  automatic 
cranking and startup, followed by automatic transfer 
to the standby source.
•  Utility  source  voltage  is  used  to  operate  a  battery
trickle charge circuit which helps to maintain battery 
state of charge during non-operating periods.
Part 3
Page 58
TRANSFER SWITCH
sEctioN 3.1
DEscriPtioN & comPoNENts