Generac Power Systems 9 kW NG ユーザーズマニュアル

ページ / 192
AC GENERATORS
sEctioN 2.4
DiaGNostic tEsts
introduction
This  section  is  provided  to  familiarize  the  service 
technician  with  acceptable  procedures  for  the  test-
ing  and  evaluation  of  various  problems  that  could  be 
encountered  on  standby  generators  with  air-cooled 
engine. Use this section of the manual in conjunction 
with  Section  2.3,  “Troubleshooting  Flow  Charts”. The 
numbered tests in this section correspond with those 
of Section 2.3.
Test procedures in this section do not require the use 
of  specialized  test  equipment,  meters  or  tools.  Most 
tests  can  be  performed  with  an  inexpensive  volt-
ohm-milliammeter  (VOM).  An  AC  frequency  meter  is 
required, where frequency readings must be taken. A 
clamp-on ammeter may be used to measure AC loads 
on the generator.
Testing  and  troubleshooting  methods  covered  in  this 
section are not exhaustive. We have not attempted to 
discuss,  evaluate  and  advise  the  home  standby  ser-
vice trade of all conceivable ways in which service and 
trouble  diagnosis  might  be  performed.  We  have  not 
undertaken  any  such  broad  evaluation.  Accordingly, 
anyone  who  uses  a  test  method  not  recommended 
herein must first satisfy himself that the procedure or 
method he has selected will jeopardize neither his nor 
the product’s safety.
SaFety
Service  personnel  who  work  on  this  equipment  must 
be  made  aware  of  the  dangers  of  such  equipment. 
Extremely  high  and  dangerous  voltages  are  present 
that can kill or cause serious injury. Gaseous fuels are 
highly  explosive  and  can  be  ignited  by  the  slightest 
spark.  Engine  exhaust  gases  contain  deadly  carbon 
monoxide  gas  that  can  cause  unconsciousness  or 
even death. Contact with moving parts can cause seri-
ous injury. The list of hazards is seemingly endless.
When  working  on  this  equipment,  use  common 
sense  and  remain  alert  at  all  times.  Never  work  on 
this  equipment  while  you  are  physically  or  mentally 
fatigued. If you don’t understand a component, device 
or system, do not work on it.
teSt 1 – check main circuit Breaker
DISCUSSION:
Often  the  most  obvious  cause  of  a  problem  is  over-
looked. If the generator main line circuit breaker is set 
to OFF or “Open”, no electrical power will be supplied 
to  electrical  loads.  If  loads  are  not  receiving  power, 
perhaps the main circuit breaker is open or has failed.
PROCEDURE:
The  generator  main  circuit  breaker  is  located  on  the 
control  panel.  If  loads  are  not  receiving  power,  make 
sure the breaker is set to “On” or “Closed”.
If  you  suspect  the  breaker  may  have  failed,  it  can  be 
tested as follows (see Figure 1):
1.  Set a volt-ohm-milliammeter (VOM) to its “R x 1” scale 
and zero the meter.
2.  With the generator shut down, disconnect all wires from 
the main circuit breaker terminals, to prevent interaction.
3.  With  the  generator  shut  down,  connect  one VOM  test 
probe  to  the Wire  11  terminal  of  the  breaker  and  the 
other test probe to the Wire E1 terminal.
4.  Set the breaker to its “On” or “Closed” position. The VOM 
should read CONTINUITY.
5.  Set  the  breaker  to  its  OFF  or “Open”  position  and  the 
VOM should indicate INFINITY.
6.  Repeat  Steps  4  and  5  with  the VOM  test  probes  con-
nected across the breaker’s Wire 44 terminal and the E2 
terminal.
RESULTS:
1.  If the circuit breaker tests good, go on to Test 2.
2.  If the breaker tests bad, it should be replaced.
OFF
WIRE 11 
TERMINAL
E1 TERMINAL
E2 TERMINAL
WIRE 44
TERMINAL
Figure 1. Generator Main Circuit Breaker Test Points
teSt 2 – check ac output VoltaGe
DISCUSSION:
A volt-ohm-milliammeter (VOM) may be used to check 
the  generator  output  voltage.  Output  voltage  may  be 
checked  at  the  unit’s  main  circuit  breaker  terminals. 
Refer  to  the  unit’s  DATA  PLATE  for  rated  line-to-line 
and line-to-neutral voltages.
Part 2
Page 41